APC ACAC75009 Datasheet

Browse online or download Datasheet for Computer liquid cooling APC ACAC75009. APC Flooded Receiver 17lb, R410A, 6" Diameter, 18" Length User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Technical Data

®—0 HzAir-Cooled/Fluid-Cooled 50/6Technical DataACRD100, ACRD101,ACRD200, ACRD201ACRD500, ACRD501,ACRD502

Page 2

InRow RD Technical Data Manual4Standard FeaturesCabinetThe frame is constructed of 16 gauge formed steel for maximum strength. The cabinet is servicea

Page 3 - Contents

5InRow RD Technical Data ManualOptional FeaturesCable Water DetectorA leak detection cable is placed on the floor or subfloor around all possi-ble lea

Page 4

InRow RD Technical Data Manual6Microprocessor ControllerMicroprocessor Controller The microprocessor controller is standard on each unit. The controll

Page 5

7InRow RD Technical Data ManualAlarmsThe microprocessor controller shall activate a visible and audible alarm in the following occurrences:All series:

Page 6

InRow RD Technical Data Manual8InRow RD ModelsExterior components: ACRD100 and ACRD200 seriesRemovable rear doorAdjustable leveling feetSide panel

Page 7 - Overview

9InRow RD Technical Data ManualInterior components (front): ACRD100 seriesElectrical control box 1 (retractable)CompressorElectrical control box 2

Page 8 - Scalable for High Density

InRow RD Technical Data Manual10Interior components (rear): ACRD100 seriesFilter/dryerHot gas bypass valvePressure transducer (2 total, located beh

Page 9 - Hot Aisle Containment System

11InRow RD Technical Data ManualInterior components (front): ACRD200 seriesElectrical control box 1 (retractable)CompressorElectrical control box 2

Page 10 - Standard Features

InRow RD Technical Data Manual12Interior components (rear): ACRD200 seriesFilter/dryerElectrical control box 2Pressure transducer (2 total, located

Page 11 - Optional Features

13InRow RD Technical Data ManualExterior components: ACRD500 seriesRemovable rear doorsCasters (all swiveling)Side panel lockDoor handle and lock

Page 12 - Microprocessor Controller

American Power Conversion Legal DisclaimerThe information presented in this manual is not warranted by the American Power Conversion Corporation to be

Page 13

InRow RD Technical Data Manual14Interior components (front): ACRD500 seriesCondensate drain panFan (2)Thermal expansion valveFan guard (2)Compres

Page 14 - InRow RD Models

15InRow RD Technical Data ManualInterior components (rear): ACRD500 seriesEvaporator coilShutoff valvesCondensate drain panAir filtersSight glass

Page 15

InRow RD Technical Data Manual16Electrical panel: ACRD100 and ACRD200 seriesLeak detector portBuilding management system (BMS) RS-485 portRemote te

Page 16

17InRow RD Technical Data ManualElectrical panel: ACRD500 seriesTransformersUser interface connectorsMain controller boardRelay boardGround lugM

Page 17

InRow RD Technical Data Manual18User interface panel: ACRD500 seriesRack inlet temperature sensors 1, 2, 3A-Link INA-Link OUTNetwork portConsole

Page 18

19InRow RD Technical Data ManualPerformance SpecificationsNet Cooling Capacity (Air and Glycol Cooled)Return Air Temperature SKU Total Capacity kW (BT

Page 19

InRow RD Technical Data Manual20Net Cooling Capacity (Water Cooled)Return Air Temperature SKU Total Capacity kW (BTU/hr) Sensible Capacity kW (BTU/hr)

Page 20

21InRow RD Technical Data ManualPerformance at Percentage of Fan SpeedACRD100 Series% Fan SpeedVoltag e/Pha se/HzL/S (SCFM)Unit Power in kWCondenser F

Page 21

InRow RD Technical Data Manual22ACRD200 Series% Fan SpeedVoltage/Phase/Hz L/S (SCFM) Unit Power in kWNet Sensible Capacity kW (BTU/h) SA Temp °C (°F)R

Page 22

23InRow RD Technical Data ManualACRD500 Series% Fan Speed Voltage L/S (SCFM) Unit Power in kWCondenser Fan Power in kWNet Sensible Capacity kW (BTU/h)

Page 23

ContentsInRow RD Technical Data ManualiOverview ... 1Scalable Solution for Crit

Page 24

InRow RD Technical Data Manual24General DataGeneral Specifications - ACRD200 SeriesData Units Water Cooled Glycol Mixture CooledNominal flow rate ente

Page 25 - Performance Specifications

25InRow RD Technical Data ManualAir CooledData SKU ValueAIR SYSTEM - FAN (Standard Filter Installed)Size - mm (in)ACRD100 200 (7.9)ACRD101 200 (7.9)AC

Page 26

InRow RD Technical Data Manual26 Electrical DataAltitude Correction FactorsRoom Condition: 72 DB/50% RHAltitude (ft) 0 1000 2000 3000 4000 5000 6000 7

Page 27 - ACRD100 Series

27InRow RD Technical Data ManualDimensional DataACRD100 and ACRD200 seriesDimensions are shown in mm (in).na2231b

Page 28 - Voltage/Phase/

InRow RD Technical Data Manual28ACRD500 seriesDimensions are shown in mm (in).na2465a

Page 29 - ACRD500 Series

29InRow RD Technical Data ManualNetShelter SX to VX Height Adapter: ACRD100 and ACRD200 seriesNetShelter SX to VX Height Adapter: ACRD500 seriesNetShe

Page 30 - General Data

InRow RD Technical Data Manual30Piping and Mechanical ConnectionsRefrigeration Piping Diagram (ACRD100 and ACRD500 series)Note: Shutoff valves shown n

Page 31 - Air Cooled

31InRow RD Technical Data ManualWater cooled piping (ACRD200 series)Note: Bottom piping shown.InRow RDGate valve*Strainer, 20 mesh*Hose bib** Fie

Page 32 - Sound Performance Data

InRow RD Technical Data Manual32Glycol cooled piping (ACRD200 series)Note: Bottom piping shown.Expansion tank*Hose bibs*Tank fill*Gate valves*Flu

Page 33 - Dimensional Data

33InRow RD Technical Data ManualTop piping and power access locations (ACRD100 series and ACRD200 series)Dimensions are shown in mm (in).Low voltage

Page 34 - ACRD500 series

InRow RD Technical Data ManualiiPerformance Specifications ... 19Net Cooling Capacity (Air and Glycol Cooled) .

Page 35

InRow RD Technical Data Manual34Bottom piping and power access locations (ACRD100 series and ACRD200 series)Dimensions are shown in mm (in).Electrica

Page 36

35InRow RD Technical Data ManualTop piping and power access locations (ACRD500 series)Dimensions are shown in mm (in).Refrigerant discharge lineRefr

Page 37 - Note: Bottom piping shown

InRow RD Technical Data Manual36Bottom piping and power access locations (ACRD500 series)Dimensions are shown in mm (in).Refrigerant liquid lineRefr

Page 38

37InRow RD Technical Data ManualOutdoor Heat ExchangersAir Cooled Condensers - Mechanical Data (ACRD100 Series)Air Cooled Condensers Mechanical Data (

Page 39

InRow RD Technical Data Manual38Air Cooled Condensers - Electrical Data (ACRD100 Series)SKU Voltage Phase Frequency FLA MCA MOPACCD75214 208-240V 1 ph

Page 40

39InRow RD Technical Data ManualACCD75201 and ACCD75204ACCD75202 and ACCD75205ACCD75203 and ACCD75206Dimensions are shown in mm (in). Conden

Page 41

InRow RD Technical Data Manual40ACCD75207ACCD75208 and ACCD75209Condensers shown above have 16 mm (0.63 in) mounting holes on each of their lower legs

Page 42

41InRow RD Technical Data ManualACCD75216, ACCD75218, and ACCD75220ACCD75217 and ACCD75219ACFC75210ACFC75255Dimensions are shown in mm (in).na2893ana2

Page 43 - Outdoor Heat Exchangers

InRow RD Technical Data Manual42ACFC75256ACFC75257Dimensions are shown in mm (in).Air-cooled Condenser FeaturesAvailable in one to three fan configura

Page 44

43InRow RD Technical Data ManualGuide SpecificationsPART 1 — GENERAL1.01 SUMMARYA. The environmental control system shall be designed specifically for

Page 45 - ACCD75203 and ACCD75206

InRow RD Technical Data ManualiiiGuide Specifications ...43Guidelines for Installation . . . . . .

Page 46 - ACCD75215

InRow RD Technical Data Manual443. All exterior panels and frame shall be powder coated for durability and attractive finish. Exterior frame and panel

Page 47 - ACFC75255

45InRow RD Technical Data Manual3. Alarms: The microprocessor controller shall activate a visible and audible alarm in the occurrence of the following

Page 48 - Air-cooled Condenser Features

InRow RD Technical Data Manual46F. Cooling Coil And Condensate Pan1. ACRD100 and ACRD200 series:a. The cooling coil shall use corrugated aluminum fin

Page 49 - Guide Specifications

47InRow RD Technical Data ManualJ. Temperature Sensors1. Internal Temperature Sensors: Thermistor temperature sensors shall be mounted behind the fron

Page 50 - 460-480V 60Hz 22

InRow RD Technical Data Manual48Guidelines for InstallationThe InRow RD provides reliable, accurate temperature control of computer rooms, laboratorie

Page 52

10/2009990-3236C-001APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following

Page 54 - Guidelines for Installation

1InRow RD Technical Data ManualOverviewThe modular, row-based computer room cooling system offers efficient, predictable, and economical cooling for a

Page 55

InRow RD Technical Data Manual2Scalable Solution for Critical EnvironmentsInRow AdvantagesThe row-based solution improves energy efficiency and coolin

Page 56 - 10/2009990-3236C-001

3InRow RD Technical Data ManualHot Aisle Containment System Modular ceiling tiles and doors can be used to enclose the hot aisle. This increases the d