Installation (continued)
Drycooler and Pump Package Connection
Provide sufficient valves and unions to isolate
the dry cooler and pump package during routine
service or in the event of an emergency.
Pipe should be welded wherever possible to
minimize leak possibility.
Pipe and wire the dry cooler/precool system in
accordance with local and national codes. A
wiring diagram is attached to the inside of each
control panel cover. The control enclosures are
weather protected and should be mounted close
to the header end of the drycooler. All
thermostats should be checked for the proper
set point per the wiring diagram. Any remote
bulb thermostats should be mounted at this time.
The pump package is weather-protected and
has been factory wired with branch fusing and
pump motor overloads. Consult the nameplate
for electrical information on the pump package
for disconnect sizing. Your pump size may have
been increased or decreased from the standard
pump package due to pressure drop
requirements.
The pump package should be mounted as close
as possible to the drycooler and the glycol
solution should flow from the drycooler to the
pump package.
The expansion tank with airtrol fitting must be
mounted at the highest point in the piping
system. A fill hose bib should also be provided
to facilitate filling the system.
Installation of an air separator will enhance the
ability to remove the air during start-up.
Air Cooled Condenser Installation
All refrigerant piping should comply with
ASHRAE, local and national codes. Use only
refrigerant grade pipe, and pipe joints should be
high temperature brazed.
The discharge line should loop above the hot
gas header at the condenser.
The risers must be properly sized to ensure oil
return.
Discharge lines should be sized to maintain
sufficient return oil to the compressor by
maintaining high gas velocity while keeping
the refrigerant pressure drop within normal
ranges.
Piping should be adequately supported and
should allow for normal expansion and
contraction.
General Air Distribution
The AFX unit provides full rated air delivery at
0.5 external static pressure. All other AFX units
are rated for 0.3” external static pressure