Refrigerant Pipe Connections;
AIR-COOLED
When piping air-cooled systems, care must be
taken to use only clean refrigerant grade (Type
L) pipe and follow standard procedures for pipe
size selection. Maximum recommended
distance between the evaporator and condenser
is 200 equivalent feet. For any run beyond this
distance contact the factory for assistance.
Vertical runs (hot gas) require a trap every 20
feet of rise.
RECOMMENDED DISCHARGE LINE SIZES
R-22
Capacity Equivalent Length, Ft.
BTU/hr 50 100 150 200
18,000 5/8 5/8 5/8 7/8
24,000 5/8 7/8 7/8 7/8
36,000 7/8 7/8 7/8 7/8
60,000 7/8 1-1/8 1-1/8 1-1/8
Recommended sizes are applicable with
evaporating temperatures from -40
o
F to 45
o
F
and condensing temperatures from 80
o
F to
130
o
F.
Water/Glycol Pipe Connections;
WATER-COOLED/GLYCOL-COOLED
Care should be taken in the correct connection
of the water/glycol inlet and outlet connections.
It is recommended that shut off valves be
installed for use during routine service and
emergency isolation of the air conditioner.
RECOMMENDED LIQUID LINE SIZES
R-22
Condenser to Evaporator
Capacity Equivalent Length, Ft.
BTU/hr 50 100 150 200
18,000 3/8 3/8 1/2 1/2
24,000 3/8 1/2 1/2 1/2
36,000 1/2 1/2 1/2 1/2
60,000 1/2 5/8 5/8 5/8
Recommended sizes are applicable with
evaporating temperatures from -40
o
F to 45
o
F
and condensing temperatures from 80
o
F to
130
o
F.