Preventive Maintenance
The operating life of the AFX Series system can
be extended by following a simple preventive
maintenance schedule. The schedule will
reduce the possibility of failure of components
and unnecessary malfunction of the system.
The service technicians must be thoroughly
familiar with the special design features of this
equipment before attempting any service or
repair.
MONTHLY
1. Check that filters are clean and in place.
2. Check that condensate drain is open.
3. Check that humidifier cylinder replacement
light it not on and verify operation of the
humidifier.
4. Check that drive belts are in good condition
and that the belt tension is correct.
5. Clean inside of unit as necessary.
6. Check that blower bearing/shaft assembly
turns freely.
7. Check unit conformance to temperature and
humidity set points.
8. Ensure heater operation.
9. Check electrical components and ensure
correct amp draws and secure connections.
10. Check the microprocessor configuration.
11. Check the microprocessor for any alarm.
SEASONALLY
1. Check electrical components for loose wire
connections.
2. Check fan(s) and drive components.
3. Complete all items listed on the monthly
checklist.
ANNUALLY
1. Thoroughly check the system and clean unit
interior.
2. Clean the cooling coil.
3. Perform all items listed on the monthly and
seasonal checklist.
BI-ANNUALLY
1. Lubricate the blower motor bearings if
applicable.
2. Perform all items listed under the preventive
maintenance schedules.