6APC NetworkAIR AFX
Microprocessor Controller
Microprocessor Controller
The microprocessor controller is
standard on the main module of
each system. The controller pro-
vides precision control for the
demanding requirements of:
Data centers
Control rooms
•Clean rooms
Switch rooms
UPS rooms
The easy-to-use display allows the
operator to select options from the
device’s menu-driven interface to
control and monitor the connected
air conditioning system.
Status
Complete status monitoring is pro-
vided within the status menu of the
microprocessor controller. Avail-
able information includes:
Current Temperature/Humidity
Temperature/Humidity Setpoint
Cooling/Heating Status
Humidification/Dehumidification
Status
Alarms
Quick access to any alarm condition
is facilitated through the menu
structure. The alarm key acts as a
hot key providing immediate access
to the alarm display menu. Presence
of a new alarm will sound the audi-
ble alarm. The red alarm LED on
the display panel will remain illu-
minated until all alarms have been
cleared. The temperature and
humidity alarm setpoints are adjust-
able. Alarm annunciations include:
Loss of airflow
Clogged filter
High head pressure
Low suction pressure
High/Low temperature
High/Low humidity
Automatic setpoint crossover pro-
tection will prevent the setting of
the heat setpoint above the cool set-
point and the humidification
setpoint above the dehumidification
setpoint. Setpoint adjustment can be
restricted to only operators with
knowledge of the security codes set
within the security menu structure.
Configuration
Flexibility is offered through he use
of the configuration menu. Operat-
ing requirements are satisfied by
changing the configuration set-
tings. New configurations are
stored in EEPROM and protected
from unauthorized tampering by the
four-digit security password,
selected in the security menu. Con-
figuration options include:
Fahrenheit or celsius display
Compressor minimum on/off time
Power loss restart time delay
Redundant unit grouping
Alarm input polarity
Alarm enable
Temperature/Humidity deadbands
Small room delay
Common Alarm Contact
A common alarm relay is installed
on every microprocessor. In the
event of an alarm condition, the
relay will change state. The user
can select which alarms change the
state of the relay. This feature
allows for remote enunciation of
alarm status.
Run Times
The major components within the
unit have independent run timers
that monitor and store accumulated
run hours on the components. The
run timers are provided with opera-
tor adjustable run time alarms.
Security
Multiple security levels prevent
unauthorized adjustment of impor-
tant system parameters. The user
may select a four-digit password for
setpoint and configuration changes.
Should the password be forgotten,
APC can provide temporary access.
Monitoring
With the addition of a supervisory
network communications card the
microprocessor may interface with
the locally installed APC remote
monitoring and control system.
Gateways are available for interfac-
ing with building management
systems. Please check with APC for
compatibility with your building
management system.
Cool Inhibit
Prevents the unit from over-cooling
during the dehumidification cycle.
If the space temperature falls below
a user adjustable setpoint, cooling
will become inhibited until the
space temperature returns to
setpoint.
Cool Override
A manual toggle switch will allow
the compressor to operate in the
event of a microprocessor failure.
The cool override can be field wired
to a snap acting thermostat for cool-
ing control.
Remote Shutdown
Events external to the unit, such as
activation of a fire suppression sys-
tem may require the unit to shut
down remotely. Additionally this
feature may be tied into a BMS that
would allow remote control of the
units on/off status.