Performance Specifications—Water Cooled
10 APC NetworkAIR™ AFX
Performance Specifications—Water Cooled
AFX MODEL AFX018 AFX065
REHEAT
Electric -- Equally Loaded Three (3) Phase, Finned Tubular, Low-Watt Density
Capacity -- BTU/HR (kW) Includes Motor Heat***** 28,000 (8.3) 85,000 (24.9)
Stages 12
Hot Water -- 180F (82.2C) EWT, 160F (71.1C) LWT
Capacity - BTU/HR (kW) Includes Motor Heat 79,000 (23.0) 268,000 (78.3)
GPM (L/s) 7.8 (0.49) 26.4 (1.67)
Pressure Drop -- PSI (kPA) 0.3 (1.8) 2.7 (18.6)
Hot Gas Reheat
Capacity -- BTU/HR (kW) Includes Motor Heat 26,000 (7.6) 147,000 (43.0)
Steam -- 15 psig (103.3 kPa)
Capacity -- BTU/HR (kW) Includes Motor Heat 79,000 (23.0) 273,000 (79.9)
Control Valve solenoid solenoid
PHYSICAL DATA
Weight -- lbs (kg) 1,000 (454) 2,700 (1,227)
Height -- Inches (mm) 76.0 (1,930) 76.0 (1,930)
Length -- Inches (mm) 34.4 (873) 98.3 (2,997)
Depth -- Inches (mm) 34.4 (873) 34.4 (873)
CONNECTION SIZES******
Water In/Out -- Inches OD 1-3/8 2-1/8
Hot Water
Supply Line -- Inches OD 5/8 7/8
Return Line -- Inches OD 5/8 7/8
Steam
Supply Line -- Inches OD 5/8 7/8
Humidifier
Supply Line -- Inches OD 1/4 1/4
Condensate Drain
Drain Line -- Inches ID 7/8 7/8
*****With equal loading on each phase, rated at 208-230V / 3-phase, 480V / 3-phase and 600V / 3-phase
******Connections sizes, not recommended piping sizes
Page view 13