APC AFX Series Specifications Page 15

  • Download
  • Add to my manuals
  • Print
  • Page
    / 46
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 14
APC NetworkAIR™ AFX 11
Performance Specifications—Glycol Cooled
AFX MODEL* AFX018 AFX065
80F DB, 67F WB (26.7C DB, 19.4C WB) 50% RH
Total - BTU/HR (kW) 74,000 (21.0) 277,000 (81.0)
Sensible - BTU/HR (kW) 63,000 (18.0) 224,000 (66.0)
75F DB, 62.5F WB (23.9C DB, 16.9C WB) 50% RH
Total - BTU/HR (kW) 67,000 (20.0) 257,000 (75.0)
Sensible - BTU/HR (kW) 62,000 (18.0) 222,000 (65.0)
75F DB, 61F WB (23.9C DB, 16.1C WB) 45% RH
Total - BTU/HR (kW) 67,000 (20.0) 252,000 (74.0)
Sensible - BTU/HR (kW) 66,000 (19.0) 241,000 (71.0)
72F DB, 60F WB (22.2C DB, 15.5C WB) 50% RH
Total - BTU/HR (kW) 64,000 (19.0) 245,000 (72.0)
Sensible - BTU/HR (kW)** 60,000 (17.0) 217,000 (64.0)
72F DB, 58.6 WB (22.2D DB, 14.8C WB) 45% RH
Total - BTU/HR (kW) 64,000 (19.0) 241,000 (71.0)
Sensible - BTU/HR (kW) 64,000 (19.0) 234,000 (69.0)
70F DB, 58.5F WB (21.1C DB, 14.8C WB) 50% RH
Total - BTU/HR (kW) 62,000 (18.0) 238,000 (70.0)
Sensible - BTU/HR (kW) 58,000 (16.0) 212,000 (62.0)
70F DB, 57.2F WB (21.1C DB, 14.0C WB) 45% RH
Total - BTU/HR (kW) 62,000 (18.0) 235,000 (69.0)
Sensible - BTU/HR (kW) 62,000 (18.0) 227,000 (67.0)
COOLANT REQUIREMENTS
THR -- MBH (kW) 107,000 (31.0) 419,000 (123.0)
105 F (40.6 C) Glycol In -- GPM (L/s) 17.2 (1.1) 65.6 (4.1)
Pressure Drop -- psig (kPa) 5.2 (36) 9.4 (65)
WATER REGULATING VALVES
Size -- 2 Way Ball Valve -- Inches, NPT (Cv)*** 1 x 1-1/4 (14) 2 x 1-1/2 (40)
Size -- 3 Way Ball Valve -- Inches, NPT (Cv)**** 1 x 1-1/4 (14) 2 x 1-1/2 (40)
AIR SYSTEM -- BELT DRIVE CENTRIFUGAL
Air Volume -- CFM (L/s) 3,600 (1,699) 12,000 (5,663)
Blower Motor -- HP (kW) 3 (2.2) 5 (3.7)
External Static Pressure -- inches of water (Pa) 0.5 (124) 0.5 (124)
Number of Blowers/Motors 13
COMPRESSOR -- SCROLL
EER 13.4 13.4
Quantity 12
EVAPORATOR COIL -- V FRAME, COPPER TUBE/ALUMINUM FIN
Face Area -- ft
2
(m
2
)
9.5 (0.88) 33.0 (3.07)
Rows Deep 44
Face Velocity -- FPM (m/s) 380 (1.93) 364 (1.85)
HUMIDIFICATION --- SOLID STATE ELECTRODE CANISTER
Flush Cycle automatic automatic
Capacity -- Lbs/hr (Kg/hr) 10 (4.5) 20 (9.0)
kW 3.4 6.8
FILTERS
Quantity 26
Depth -- Inches (mm) 4 (102) 4 (102)
Size (Downflow) -- Inches (mm) 30 x 15.5 (762 x394) 30 x 15.5 (762 x394)
Size (Upflow) -- Inches (mm) 27 x 18 (686 x457) 27 x 18 (686 x457)
REHEAT
Electric -- Equally Loaded Three (3) Phase, Finned Tubular, Low-Watt Density
Capacity -- BTU/HR (kW) Includes Motor Heat***** 28,000 (8.3) 85,000 (24.9)
Stages 12
Hot Water -- 180F (82.2C) EWT, 160F (71.1C) LWT
Capacity - BTU/HR (kW) Includes Motor Heat 79,000 (23.0) 268,000 (78.3)
GPM (L/s) 7.8 (0.49) 26.4 (1.67)
Pressure Drop -- PSI (kPA) 0.3 (1.8) 2.7 (18.6)
Hot Gas Reheat
Capacity -- BTU/HR (kW) Includes Motor Heat 26,000 (7.6) 147,000 (43.0)
Steam -- 15 psig (103.3 kPa)
Capacity -- BTU/HR (kW) Includes Motor Heat 79,000 (23.0) 273,000 (79.9)
Control Valve solenoid solenoid
*Rated Capacity +/-10%
**Nominal Rating Point
***2-Way Single Seated, 400 psig W.W.P. max
****3-Way Single Seated, 400 psig W.W.P. max
*****With equal loading on each phase, rated at 208-230V / 3-phase, 480V / 3-phase and 600V / 3-phase
Page view 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 45 46