APC NetworkAIR™ AFX 21
Fluid Coolers
Glycol-cooled fluid cooler—performance/electrical data
OHE SKU Voltage
Ambient
Temperature
40%
Ethylene
Glycol@
130F
Air Quantity
Feeds
Fan/Motor
Connect
-ions
Weight
Glycol
Volume
Electrical Data
95F 105F PD(ft) CFM L/s Qty HP RPM Lbs Kg Gal L FL MC MO
ACFC75116 208-230/3/60
018 018 25.7@20 10,100 4,766 12 2 1/3 1140 (2) 1-3/8 450 204 4.9 18.1 5.2 5.9 15.0
ACFC75117 480/3/60
018 018 25.7@20 10,100 4,766 12 2 1/3 1140 (2) 1-3/8 450 204 4.9 18.1 2.6 2.9 15.0
ACFC75242 600/3/60
018 018 25.7@20 10,100 4,766 12 2 1/3 1140 (2) 1-3/8 450 204 4.9 18.1 2.1 2.4 15.0
ACFC75144 208-230/3/60
065 N/A 20.7@70 32,900 15,526 21 3 1-1/2 1140 (2) 2-5/8 2360 1070 13.0 49.2 21.0 22.8 25.0
ACFC75145 480/3/60
065 N/A 20.7@70 32,900 15,526 21 3 1-1/2 1140 (2) 2-5/8 2360 1070 13.0 49.2 10.5 11.4 15.0
ACFC75251 600/3/60
065 N/A 20.7@70 32,900 15,526 21 3 1-1/2 1140 (2) 2-5/8 2360 1070 13.0 49.2 8.4 9.1 15.0
ACFC75153 208-230/3/60
N/A 065 16.3@70 43,900 20,716 21 4 1-1/2 1140 (2) 2-5/8 1620 735 16.7 63.2 28.0 29.8 35.0
ACFC75154 480/3/60
N/A 065 16.3@70 43,900 20,716 21 4 1-1/2 1140 (2) 2-5/8 1620 735 16.7 63.2 14.0 14.9 15.0
ACFC75254 600/3/60
N/A 065 16.3@70 43,900 20,716 21 4 1-1/2 1140 (2) 2-5/8 1620 735 16.7 63.2 11.2 11.9 15.0
FLA = Full Load Amps
MCA = Minimum Circuit Amperes
MOP = Maximum Overcurrent Protection
*Fluid coolers can be selected for multiple indoor air conditioning units from the factory. Consult factory for help configuring many-to-one or one-to-
many glycol loops.