24 APC NetworkAIR™ AFX
Pump Specifications
Pump performance
Pump connection sizes
Pump electrical data
HP (kW) 3/4 (.56) 3 (2.2)
LINE Suction Discharge Suction Discharge
Size (inches) 1-1/4 1 2 1-1/2
HP (kW) 3/4 (.56) 3 (2.2)
VOLTAGE FLA MCA FLA MCA
208-230/3/60 3.5 4.4 8.2 10.3
480/3/60 1.6 2.0 3.8 4.8
*Values are calculated based on 3-phase power.
FLA = Full Load Amperes
MCA = Minimum Circuit Amperes
20
30
50
60
10
70
80
90
100
110
120
40
0
25
30
35
40
5
10
15
20
TOTAL DYNAMIC HEAD IN FEET
BHP ABSORBED
20 30 50 6010 70 80 90 10040
CAPACITY IN U.S. GALLONS PER MINUTE
0 1.0 2.0 3.0 4.0 5.0 7.0
20
30
50
60
10
70
80
90
100
40
PERCENT EFFICIENCY
CAPACITY IN LITERS PER SECOND
3600 R.P.M.
6.0 8.0 9.0 10
110 120 130
130
3 HP
0.75 HP