APC AFX Series Specifications Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 46
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
2APC NetworkAIR AFX
Standard Features
Cabinet
The frame is constructed of heavy
gauge steel for maximum strength.
Steel access panels are insulated for
quieter operation. The unit has been
designed for full service access
from the front. The flush mounted
panels are removable using conve-
nient quarter-turn fasteners. The
access doors for the electronic con-
troller and electrical panel can be
opened without interrupting the
operation of the unit.
Evaporator Coil/Drain Pan
AFX utilizes dual distributors on
one circuit of the refrigeration sys-
tem. During dehumidification the
smaller distributor is turned off,
effectively reducing the active cir-
cuits of the evaporator coil. During
this mode of operation the evaporat-
ing temperature is decreased,
resulting in a lower coil surface
temperature. This decreases the
sensible heat ratio of the coil allow-
ing a greater percentage of moisture
removal. Additionally, the warmer
air leaving the inactive circuits of
the evaporator coil blends with the
near saturated air from the active
circuits raising the dry bulb temper-
ature of the blended air well above
saturation. Evaporator is a “V”coil,
1/2” rifled, copper tube, with raised,
lanced, rippled, aluminum fins.
Condensate pan is constructed of
stainless steel.
Humidifier
The humidifier utilizes a pure steam
generator specifically designed for
hi-tech area environmental control.
Pure steam eliminates contaminat-
ing mineral deposits, bacteria, white
dust and excessive humidity. Auto-
matic flushing combined with an
indicator that signals when the can-
ister is to be change changed,
ensure maintenance free operation.
Electrical Panel
The electrical panel contains the
contactors, starters, overload pro-
tection devices, and input power
disconnects. Each wire (except
jumpers) is numbered every 3”
(80mm), or color coded to facilitate
circuit tracing when installing and
servicing the unit. Each AC power
circuit is individually branch circuit
fused on all three phases. All com-
pressor and motor devices are
thermally and short circuit pro-
tected. The electrical panel is easily
accessible from the front of the unit.
An emergency cool override switch
can be manually activated to initiate
cooling and a field wired thermostat
can be utilized to control cooling
operation. Electrical components
are UL-listed and -recognized and
all wiring conforms to NFPA 70
(NEC) and UL 1995 requirements.
Air Filter
The filtration of conditioned air is
extremely vital to maintaining the
clean, particle-free environment
required by electrical equipment.
The system uses 30% efficient (100
microns) (ASHRAE 52.1-92), 4”
(102 mm) deep filters, with full
depth pleats. Deeper filters produce
a lower pressure drop, requiring
less energy during normal opera-
tion. Filters are replaceable through
the front of the upflow unit and the
top of the downflow unit.
Electric Reheat
A three-phase electrical resistance
heater sized to offset the sensible
cooling capacity in the dehumidifi-
cation mode is incorporated in each
NetworkAIR AFX. The reheat ele-
ments are low watt density sheathed
components. The reheat is 3- phase
to provide even phase loading.
Reheat elements are electrically and
thermally protected. The AFX18 is
one stage and AFX65 is two stages.
Fan/Motor Section
The NetworkAIR AFX includes
centrifugal blower assemblies that
have been engineered for quiet, reli-
able operation. Lower blower
speeds reduce noise and extend belt
and bearing life to 200,000L
10
hours. Permanently lubricated bear-
ings, a single-belt variable pitch
drive, and an adjustable motor base
all ensure dependable operation. In
addition, the return air is evenly dis-
tributed across the cooling coil.
Main Power Disconnect
A nonautomatic main power circuit
breaker disconnects all high voltage
power to the unit. The disconnect
switch is accessible without remov-
ing the electric box cover.
Refrigeration System and
Compressor
The refrigeration system operates
under an automatic microprocessor
controller for greater efficiency and
accuracy. The heavy-duty compres-
sor is designed for year-round
operation with a 15-year life
expectancy. Performance of the
refrigeration system is enhanced by
use of Scroll Compressor Technol-
ogy. Vibration in the system is
greatly reduced by eliminating
reciprocating masses found in the
semi-hermetic compressor. Risk of
refrigeration leaks at compressor
gaskets are eliminated with the
compressors’ fully welded hermetic
shell. The design of the scroll is
more tolerant to liquid flood back
than the traditional reciprocating
compressor. Power consumption at
full load is greatly reduced with
higher EER’s of the scroll. In addi-
tion reliability is enhanced due to
the fewer moving parts required
using scroll technology. The end
result is a refrigeration system that
offers the user optimized perfor-
mance, efficiency, and reliability.
Page view 5
1 2 3 4 5 6 7 8 9 10 11 ... 45 46

Comments to this Manuals