Optional Features
APC NetworkAIR™ AFX 5
Floorstand
The floorstand raises the unit above
the subfloor to match the height of
the raised floor. Heights are avail-
able (from 6” (142 mm) to 36” (914
mm)) in 3” (76.2 mm) increments
and are adjustable +/- 1.5” (38.1
mm). APC recommends at least 12”
(305 mm) high floorstands for their
downflow units. Adjustment is pro-
vided by threaded pedestals.
Vibration absorbing pads are
included. The floorstand, pedestal,
and pads ship loose. In areas where
earthquakes are a concern, seismic
floorstands are available in 12”
(305mm), 18” (457 mm) and 24”
(610 mm) heights.
Environmental Management
System
A browser-accessible, 1U, rack-
mountable appliance allows
monitoring of environmental condi-
tions. Monitoring of one
temperature, one humidity, and one
vibration sensor ship standard.
When conditions change, notifica-
tions are sent via email to
appropriate personnel. The EMS
provides 8 input contacts, 2 output
relays, and controllable power out-
lets for defining actions remotely
should conditions warrant it.
ModBus/JBus Gateway
The Gateway translates transmis-
sion protocol from the system’s
network into ModBus/JBus com-
munication protocol. One gateway
can support up to 16 units.
Custom Alarm Contact Closures
Each unit is equipped with dry con-
tact closures. Upon activation of the
associated alarm, a discreet Nor-
mally open or Normally closed
contact is available for remote mon-
itoring of that discrete alarm.
Downflow Return Duct
A return duct the length and width
of the unit may be field installed on
a downflow unit to provide conve-
nient connection to external
ductwork.
Casters
A set of 6” plated rolling caster
wheels are available for handling of
equipment.