15Remote Air Cooled Condenser
Adjusting the S350A/B
Refer to the following steps for adjusting stage module settings.
Electrical Hazard:
Disconnect power supply to avoid possible electrical shock or
equipment damage. More than one disconnect may be required to completely de-energize
equipment.
1. Ensure all power to system is off. Each stage module may be receiving power from separate
sources. Make sure all power sources to each stage module are off.
2. Remove the stage module cover by loosening the four captive cover screws.
3. Set the heating/cooling jumper blocks to the desired mode of operation. Position the jumper
blocks vertically for heating or horizontal for cooling.
4. Adjust the differential using the potentiometer marked DIFF to the desired setting (the difference
in degrees [3°F] between energizing and de-energizing the stage module relay).
5. Use the potentiometer marked OFFSET to adjust the offset to the number of degrees from the
System 350 control setpoint at which the stage relay de-energizes.
6. Replace the cover on the stage module and fasten it in place with screws.
7. Restore power to system.