APC AFX Series Technical Information Page 19

  • Download
  • Add to my manuals
  • Print
  • Page
    / 23
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 18
Remote Air Cooled Condenser16
Default jumper settings for “heating”, relay NC
Mode
Fan
Connection
Sensor
Reading Relay
Fan
Status
Standard
Operation
Control
Failure
Heating NC to C Below
Setpoint
Energized OFF Will drive
head pressure
toward
setpoint.
May drive
head
pressure
below
desired
level.
Heating NC to C Above
Setpoint
De-energized ON
Model
LNH 1140 rpm Larkin
Condensers
Fan Config.
1×N or 2×N
A350 Set
Point
S1 ºC (°F)
S350
**
OFFSET S2
(°F)
S350
**
OFFSET S3
(°F)
FM35 LNH-S01-A007 12FPI 1 × 1 x x x
LNH-S01-A011 12FPI 1 × 2 90 x x
LNH-S02-A017 12FPI 1 × 2 100 x x
FM40 LNH-S02-A011 12FPI 1 × 2 87 x x
LNH-S02-A017 12FPI 1 × 2 95 x x
LNH-S02-A026 12FPI 1 × 3 110 12 x
FM50 LNH-S02-A011 12FPI 1 × 2 77 x x
LNH-S02-A017 12FPI 1 × 2 90 x x
LNH-S02-A026 12FPI 1 × 3 100 10 x
AFX018
LNH-S01-A007 12FPI 1 × 1 x x x
LNH-S01-A007 12FPI 1 × 1 x x x
LNH-S02-A011 12FPI 1 × 2 95 x x
AFX065
LNH-S02-A017 12FPI 1 × 2 70 x x
LNH-S03-A026 12FPI 1 × 3 96 20 x
LNH-D06-A044 2 × 3 100 10 x
Note:** Larkin wires A350A/B and S350A/B as NC, jumper positions in A350A/B and S350A/B as
heating.