19Remote Air Cooled Condenser
Jumper set as “cooling”, relay NO
Electrical Hazard: Ensure all power is off. It may be necessary to perform more than one
disconnect to de-energize the system.
1. Remove the stage module cover by loosening the four cover screws.
2. Using the potentiometer on the right, adjust the differential to 3°F.
3. Using the potentiometer on the left, adjust the offset to the desired setting (the difference in
degrees).
4. Replace the cover, fasten in place with screws, and restore power to the system.
Model Condenser Model
Fan Config. 1
× N
A350 Set
Point
S1 (°F)
S350
**
OFFSET
S2 (°F)
S350
**
OFFSET S3
(°F)
FM35
LNH-S01-A007 12FPI 1 × 1 x x x
LNH-S01-A011 12FPI 1 × 2 87 x x
LNH-S01-A017 12FPH 1 × 2 97 x x
FM40
LNH-S02-A011 12FPI 1 × 2 84 x x
LNH-S02-A017 12FPI 1 × 2 92 x x
LNH-S03-A026 12FPI 1 × 3 95 12 x
FM50
LNH-S02-A011 12FPI 1 × 2 74 x x
LNH-S02-AP17 12FPI 1 × 2 87 x x
LNH-S03-A026 12FPI 1 × 3 87 10 x
AFX018
LNH-S01-A007 12FPI 1 × 1 x x x
LNH-S01-A007 12FPI 1 × 1 x x x
LNH-S01-A011 12FPI 1 × 2 92 x x
AFX065
LNH-S02-A017 12FPI 1 × 2 67 x x
LNH-S03-A026 12FPI 1 × 3 72 20 x
LNH-D06-A044 2 × 3 87 10 x
**
Larkin wires A350A/B and S350A/B as NO, jumper positions in A350A/B and S350A/B as cooling.