Installation ManualUniflair™ LE Accessories990-5565-001Publication Date: May 2014
Uniflair LE Accessories Manual8NOTE: For installation on a raised floor, install a flexible seal (field supplied) at least 5.59 mm (0.2 in.) thick bet
Worldwide Customer SupportCustomer support for this or any other product is available at no charge in any of the following ways:• Visit the Schneider
9Uniflair LE Accessories Manual12-in.,18-in., 24-in., 36-in., Seismic FrameThe following tables provide frame size, model, and fastener details for th
Uniflair LE Accessories Manual10Seismic analysis of Uniflair floor stands A structural analysis model was created for each of the frames for the Unif
11Uniflair LE Accessories ManualUniflair Plenums20-in. Return Plenum (Non-Stackable)WARNINGHEAVY EQUIPMENTUse at least two people when handling and in
Uniflair LE Accessories Manual12NOTE: Fasteners are field supplied.The following table provides frame size and model details for the Uniflair plenums.
13Uniflair LE Accessories Manual12-in. Plenum (Stackable Up To 48-in.)Up to four 12-in. plenums can be stacked together. NOTE: Fasteners are field sup
Uniflair LE Accessories Manual14The following table provides frame size, model, and fastener details for 12-in. plenums (stackable up to 1219.2 mm (48
15Uniflair LE Accessories Manual20-in. Front Supply Plenum w/ GrilleThe following table provides frame size and model details for the 20-in. front sup
17Uniflair LE Accessories ManualUniflair Sub-Bases8-in. Sub-Base for PipingNOTE: Fasteners and vibration pads are field supplied.WARNINGHEAVY EQUIPMEN
Schneider Electric IT Corporation Legal DisclaimerThe information presented in this manual is not warranted by the Schneider Electric IT Corporation t
Uniflair LE Accessories Manual18The following tables provide frame size, model, and fastener numbers for the 8-in. sub-base for piping.Type of Plenum
19Uniflair LE Accessories Manual20-in. Sub-Base for Piping NOTE: Vibration pads and fasteners are field supplied.The following tables provide frame si
Uniflair LE Accessories Manual2020-in. Sub-Base (Front Supply w/ Grille) na4545a500 MM (20-IN.) SUB-BASEM8 FASTENERS
21Uniflair LE Accessories ManualNOTE: Vibration pads and fasteners are field supplied.The following table provides frame size, model, and fastener det
23Uniflair LE Accessories ManualDamper UtilizationOverviewSchneider Electric offers the following types of dampers:• Motorized Damper• Gravity Dampe
Uniflair LE Accessories Manual24Installation ConfigurationDamper motor 1Damper 1DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASHTurn off all
25Uniflair LE Accessories Manual1. Turn power off to the unit.2. The following electrical diagrams provide SKU and wiring details to wire the damper t
Uniflair LE Accessories Manual26NOTE: The password is found inside the envelope attached to the manual. If the password has been changed, enter the ne
27Uniflair LE Accessories ManualGravity DamperInventoryWARNINGHEAVY EQUIPMENTUse at least two people when handling and installing this equipment.Failu
Table of ContentsUniflair LE Accessories Manual iSafety ...
29Uniflair LE Accessories ManualCondensate PumpsOverviewUniflair condensate removal pumps collect and automatically remove water up to 100°C (212°F).
Uniflair LE Accessories Manual30Component IdentificationItem DescriptionElectrical component coverMotor (for voltages, see “Pump Models and SKUs” on
31Uniflair LE Accessories ManualPump Models and SKUsThe following table provides the model numbers, SKU, installation details of pumps available for U
Uniflair LE Accessories Manual322. Install flexible tubing or pipe from the pump to the drain inlet hole. Make sure the pipe does not interfere with t
33Uniflair LE Accessories ManualThe following diagram provides a general diagram of wiring to the pump motor to the unit. This diagram is also located
Uniflair LE Accessories Manual343. Connect the pump high float switch that leads to Digital Input 2 on the Uniflair unit (in series with leak detectio
35Uniflair LE Accessories Manual3. Connect the pump high float switch that leads to Digital Input 2 on the Uniflair unit (in series with leak detectio
Uniflair LE Accessories Manual36Using the touchscreen display Path: Main > Configuration > Unit > Digital Inputs1. Turn power on to the unit
37Uniflair LE Accessories ManualNOTE: In case of extreme algae formation, unplug the pump and fill the reservoir with a commercially available algaeci
ii Uniflair LE Accessories ManualGravity Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Inventory
39Uniflair LE Accessories ManualSmoke and Fire SensorsInventory NOTE: Inspect for missing components. If parts are missing, contact Schneider-Electric
Uniflair LE Accessories Manual40na4806aMODEL TD/UAV 0511 - 0611TD/UWV 0511 - 0611TD/UEV 0511 - 0611TD/UDV 0511 - 0611TD/UTV 0511 - 0611na4807aMODELTD/
41Uniflair LE Accessories Manualna4805aMODELTD/UAV 0921 - 1822TD/UWV 0921 - 1822TD/UEV 0921 - 1822TD/UDV 0921 - 1822TD/UTV 0921 - 1822TUAV 2242 - 3342
Uniflair LE Accessories Manual422. Remove any necessary unit paneling and/or filters to access the bracket installation location.3. Secure the bracket
43Uniflair LE Accessories Manual123456123456UPC1s; UPC1m+ VDC GND ID452 2046522025na4790aSMOKESFFS000000(New Model)FIRESFFS000000(New Mo
Uniflair LE Accessories Manual44The following graphic provides details to wire the smoke and fire detectors in 24 V series.5. Locate the terminal conn
45Uniflair LE Accessories Manual4. Press ENTER.5. Select HARDWARE SETTINGS and press ENTER.6. Navigate to “DIGITAL INPUT 4 CONFIGURATION”. 7. Check to
Uniflair LE Accessories Manual4624 V Relay for External Smoke/Fire Alarm Inventory Installation1. Locate the mounting location based on the unit model
47Uniflair LE Accessories ManualIGCNV1CNV2TR3TR2SM5SM4TRFSPFSCUTAMCVUPC1sJ1J12 J13 J15J14J11J5J4J2 J3FUSEJ9M6M10M11 M14 M7M9M3M5M2M1M12M8J1CPYSELF1RFS
Uniflair LE Accessories Manual iiiInstallation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61Coo
Uniflair LE Accessories Manual48PANELna4818aRFFF5F6MODELTD/UAV 0921 - 1822TD/UWV 0921 - 1822TD/UEV 0921 - 1822TD/UDV 0921 - 1822TD/UTV 0921 - 1822PANE
49Uniflair LE Accessories Manual2. Attach the relay socked and terminal blocks to the DIN rail.PANELna4824aPANELPANELRFFRSF F1IGRSFMODELTD/UAV 0511 -
Uniflair LE Accessories Manual503. Connect wire 20 and 52 on the labeled terminal blocks inside the electrical box. Wire routing may be needed on some
51Uniflair LE Accessories ManualWater Leak DetectorsInventoryInstallation1. Locate the correct unit type from the diagrams below to find the installat
Uniflair LE Accessories Manual52 PANELna4825aSASMODELTD/UCV1000TD/UCV1200TD/UCV1700TD/UCV2500TD/UCV3400TD/UCV4000TDCV 4300PANELna4824aPANELPANELRFFRSF
53Uniflair LE Accessories ManualPANELna4825aSASMODELTD/UAV 0921 - 1822TD/UWV 0921 - 1822TD/UEV 0921 - 1822TD/UDV 0921 - 1822TD/UTV 0921 - 1822PANELna4
Uniflair LE Accessories Manual542. Install the SAS module in the proper location on the DIN rail.3. The following provides wiring diagrams based on un
55Uniflair LE Accessories ManualSASRED 20RED 0RED 720RED 51UPC5+mID2730CP-5P720CP-4JUMPER512020CPU9V9720730PESASRED 20RED 0RED 720RED 51UPC5+mID2730CP
Uniflair LE Accessories Manual56SASRED 20RED 0RED 720RED 51UPC5+mID2730CP-5P720CP-472051SAS5120205 6 7 8CPU9V9720730PEna4813aFLOODING D
57Uniflair LE Accessories Manual4. The sensor is normally closed, and the alarm activates when the circuit is completed by either the spot or tape det
iv Uniflair LE Accessories ManualRS232 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92Inv
Uniflair LE Accessories Manual586. The tape sensor provides water leak detection along the entire length of the strip and can be placed on the floor o
59Uniflair LE Accessories ManualConfigurationUsing the LED display 1. Turn on the power to the unit and wait for the main screen to appear on the disp
61Uniflair LE Accessories ManualAutomatic Floor Pressurization SystemOverviewThe Automatic Floor Pressurization System (AFPS) (ACAC76128) maintains ai
Uniflair LE Accessories Manual62Cooling Unit Shutdown1. From the display interface, put the unit in stand-by and wait for the fans to stop.2. Turn the
63Uniflair LE Accessories Manual2. Align the mounting bracket with the unit bracket, and install with provided screws.3. Using a standard screwdriver,
Uniflair LE Accessories Manual64NOTE: Do not place the positive pressure sensor head under the raised floor where the airflow velocity is high. For ex
65Uniflair LE Accessories ManualNOTE: Ensure that the wall-mounted sensor is installed away from direct airflow to ensure proper pressurization detect
Uniflair LE Accessories Manual663. Attach the grounding wire from the harness to the grounding screw on the unit.4. Attach the electrical wires to the
67Uniflair LE Accessories ManualTransducerRange Begin: The starting value of the transducer.Range End: Ending value of the transducer.Read Value: The
5Uniflair LE Accessories ManualSafety Important Safety InformationRead the instructions carefully to become familiar with the equipment before trying
Uniflair LE Accessories Manual686. To exit, press the ESC key and navigate to the main screen.Using the touchscreen Path: Main > Configuration >
69Uniflair LE Accessories ManualLocal Values: Fan speed modulation is controlled by the pressure reading taken by the sensor on each unit.Mean Values:
Uniflair LE Accessories Manual70Rotation Weekday: Enter the required day5. Press the Home button to return to the main screen.
71Uniflair LE Accessories ManualCommunications CardsThe Carel™ pCOWeb controller provides slots for the following communications cards:NOTE: Only one
Uniflair LE Accessories Manual72Inventory Installing the pCOWeb cardEach pCOWeb is uniquely distinguished by its own Media Access Control (MAC) addres
73Uniflair LE Accessories Manual3. Insert the pCOWeb card into the pCO controller and ensure it is fully seated.4. Secure the pCOWeb card to the pCO c
Uniflair LE Accessories Manual74User interface buttons and LEDsThe pCOWeb features a push button and two indicator lights (Status LED and Ethernet LED
75Uniflair LE Accessories ManualEthernet LED Displays the status of the physical network connection (Ethernet connection signals), regardless of wheth
Uniflair LE Accessories Manual766. If not already selected, select the Internet Protocol (TCP/IP) check box.7. Select Properties. The Internet Protoco
77Uniflair LE Accessories Manual4. Select Configuration from the menu at the left of the screen.5. Select the Network tab. 6. Enter the IP Address (ex
Uniflair LE Accessories Manual6General Information OverviewThis manual provides information on accessories available with Uniflair™ LE cooling units.
Uniflair LE Accessories Manual78NOTE: Some FTP clients do not use the request from pCOWeb to open the user memory for "httpadmin" (/usr/loca
79Uniflair LE Accessories Manual5. Wait two minutes to allow the system to reboot.Verifying setup 1. To check that the procedure has been carried out
Uniflair LE Accessories Manual80LON NETWORK PCO10000F0 LonWorks® pCO system serial card (ACAC76124)NOTE: All LON cards are programed at the factory.El
81Uniflair LE Accessories Manual1. Disconnect the power.2. Using a screwdriver, remove the plastic hatch from the electronic controller.3. Using cutti
Uniflair LE Accessories Manual82Activating the service pinTo activate the service pin, short-circuit the two pins using the tip of a screwdriver. Acti
83Uniflair LE Accessories ManualUsing the touchscreen Path: Main > Configuration > Unit > Communication 1. Turn on the power to the unit and
Uniflair LE Accessories Manual84NOTE: pCOnet is not compatible with the pCO series pCOnet that features Master/Slave operation.InventoryInstallation1.
85Uniflair LE Accessories Manual4. Insert the required jumpers. The following graphic provides jumper connection details.• Jumpers P1, P2, and P3 are
Uniflair LE Accessories Manual86NOTE: Settings may appear on a different screen.2. Enter your credentials and begin configuration.BMS1 Serial Address:
87Uniflair LE Accessories ManualUsing the push button The push button restarts the pCOnet controller and recalls the factory configuration.Restarting
7Uniflair LE Accessories ManualUniflair Floorstands36-in. Welded FrameWARNINGHAZARD FROM MOVING PARTSKeep hands, clothing, and jewelry away from movin
Uniflair LE Accessories Manual88Device Instance: The number that uniquely identifies a device inside the BACnetÆË network (the BACnetÆË network can al
89Uniflair LE Accessories ManualRS485 PCOS004850 serial card for pCO controller (Part # 0M-21AS108CDZ) Electrical damage on the electronic components
Uniflair LE Accessories Manual90The PCOS004850 is an optional communication card for the pCO series controls which allows you to directly interface th
91Uniflair LE Accessories ManualIf the card is placed in the last position of the supervision serial line, pins 2 and 3, you must connect a 120-Ω1/4 W
Uniflair LE Accessories Manual92RS232PCO100MDM0/ RS232 field bus card for pCO1 (ACAC76125)Electrical damage on the electronic components usually occur
93Uniflair LE Accessories ManualInstallation1. Disconnect the power.2. Using a screwdriver, remove the plastic hatch from the electronic controller.3.
Uniflair LE Accessories Manual94Configuring using the LED displayNOTE: If installing multiple units on the network, each unit needs a unique address t