APC ACRD500 Service Manual

Browse online or download Service Manual for Heat pumps APC ACRD500. APC ACRD500 Technical data User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Technical Data

®—0 HzAir-Cooled/Fluid-Cooled 50/6Technical DataACRD100, ACRD101,ACRD200, ACRD201ACRD500, ACRD501,ACRD502

Page 2

InRow RD Technical Data Manual2Scalable Solution for Critical EnvironmentsInRow AdvantagesThe row-based solution improves energy efficiency and coolin

Page 3

3InRow RD Technical Data ManualHot Aisle Containment System Modular ceiling tiles and doors can be used to enclose the hot aisle. This increases the d

Page 4

InRow RD Technical Data Manual4Standard FeaturesCabinetThe frame is constructed of 16 gauge formed steel for maximum strength. The cabinet is servicea

Page 5 - Contents

5InRow RD Technical Data ManualNetwork Management CardThe Network Management Card (NMC) allows communication with the Local Area Network (LAN). In add

Page 6

InRow RD Technical Data Manual6Optional FeaturesCable Water DetectorA leak detection cable is placed on the floor or subfloor around all possi-ble lea

Page 7

7InRow RD Technical Data ManualMicroprocessor ControllerMicroprocessor Controller The microprocessor controller is standard on each unit. The controll

Page 8

InRow RD Technical Data Manual8AlarmsThe microprocessor controller shall activate a visible and audible alarm in the following occurrences:All series:

Page 9 - Overview

9InRow RD Technical Data ManualInRow RD ModelsExterior components: ACRD100 and ACRD200 seriesRemovable rear doorAdjustable leveling feetSide panel

Page 10 - Environments

InRow RD Technical Data Manual10Interior components (front): ACRD100 seriesElectrical control box 1 (retractable)CompressorElectrical control box 2

Page 11 - Hot Aisle Containment System

11InRow RD Technical Data ManualInterior components (rear): ACRD100 seriesFilter/dryerHot gas bypass valvePressure transducer (2 total, located beh

Page 12 - Standard Features

American Power Conversion Legal DisclaimerThe information presented in this manual is not warranted by the American Power Conversion Corporation to be

Page 13 - Remote Temperature

InRow RD Technical Data Manual12Interior components (front): ACRD200 seriesElectrical control box 1 (retractable)CompressorElectrical control box 2

Page 14 - Optional Features

13InRow RD Technical Data ManualInterior components (rear): ACRD200 seriesFilter/dryerElectrical control box 2Pressure transducer (2 total, located

Page 15 - Microprocessor Controller

InRow RD Technical Data Manual14Exterior components: ACRD500 seriesRemovable rear doorsCasters (all swiveling)Side panel lockDoor handle and lock

Page 16

15InRow RD Technical Data ManualInterior components (front): ACRD500 seriesCondensate drain panFan (2)Thermal expansion valveFan guard (2)Compres

Page 17 - InRow RD Models

InRow RD Technical Data Manual16Interior components (rear): ACRD500 seriesEvaporator coilShutoff valvesCondensate drain panAir filtersSight glass

Page 18

17InRow RD Technical Data ManualElectrical panel: ACRD100 and ACRD200 seriesLeak detector portBuilding management system (BMS) RS-485 portRemote te

Page 19

InRow RD Technical Data Manual18Electrical panel: ACRD500 seriesTransformersUser interface connectorsMain controller boardRelay boardGround lugM

Page 20

19InRow RD Technical Data ManualUser interface panel: ACRD500 seriesRack inlet temperature sensors 1, 2, 3A-Link INA-Link OUTNetwork portConsole

Page 21

InRow RD Technical Data Manual20Performance SpecificationsNet Cooling Capacity (Air and Glycol Cooled)Return Air Temperature SKU Total Capacity kW (BT

Page 22

21InRow RD Technical Data ManualNet Cooling Capacity (Water Cooled)Return Air Temperature SKU Total Capacity kW (BTU/hr) Sensible Capacity kW (BTU/hr)

Page 24

InRow RD Technical Data Manual22Performance at Percentage of Fan SpeedACRD100 Series% Fan SpeedVoltage/Phase/HzL/S (SCFM)Unit Power in kWCondenser Fan

Page 25

23InRow RD Technical Data ManualACRD200 Series% Fan SpeedVoltage/Phase/Hz L/S (SCFM)Unit Power in kWNet Sensible Capacity kW (BTU/h)SA Temp °C (°F)Ret

Page 26

InRow RD Technical Data Manual24ACRD500 Series% Fan Speed Voltage L/S (SCFM)Unit Power in kWCondenser Fan Power in kWNet Sensible Capacity kW (BTU/h)S

Page 27

25InRow RD Technical Data ManualGeneral DataGeneral Specifications - ACRD200 SeriesData Units Water Cooled Glycol Mixture CooledNominal flow rate ente

Page 28 - Performance Specifications

InRow RD Technical Data Manual26Air-CooledData SKU ValueAIR SYSTEM - FAN (Standard Filter Installed)Size - mm (in)ACRD100 200 (7.9)ACRD101 200 (7.9)AC

Page 29

27InRow RD Technical Data ManualAltitude Correction FactorsRoom Condition: 72 DB/50% RHAltitude (ft)0 1000 2000 3000 4000 5000 6000 7000 8000 9000 100

Page 30 - ACRD100 Series

InRow RD Technical Data Manual28 Electrical DataSKU MCA MOP FLACompressorPowerLRA RLAACRD100208-240V, 60Hz25 40 N/A 87.5 16.0 4.6ACRD101220-240V, 50Hz

Page 31 - ACRD200 Series

29InRow RD Technical Data ManualDimensional DataACRD100 and ACRD200 seriesDimensions are shown in mm (in).na2231b

Page 32 - ACRD500 Series

InRow RD Technical Data Manual30ACRD500 seriesDimensions are shown in mm (in).na2465a

Page 33 - General Data

31InRow RD Technical Data ManualNetShelter SX to VX Height Adapter: ACRD100 and ACRD200 seriesNetShelter SX to VX Height Adapter: ACRD500 seriesNetShe

Page 35 - Sound Performance Data

InRow RD Technical Data Manual32Piping and Mechanical ConnectionsRefrigeration Piping Diagram (ACRD100 and ACRD500 series)Note: Shutoff valves shown n

Page 36 - Electrical Data

33InRow RD Technical Data ManualWater cooled piping (ACRD200 series)Note: Bottom piping shown.InRow RDGate valve*Strainer, 20 mesh*Hose bib** Fie

Page 37 - Dimensional Data

InRow RD Technical Data Manual34Glycol cooled piping (ACRD200 series)Note: Bottom piping shown.Expansion tank*Hose bibs*Tank fill*Gate valves*Flu

Page 38 - ACRD500 series

35InRow RD Technical Data ManualTop piping and power access locations (ACRD100 series and ACRD200 series)Dimensions are shown in mm (in).Low voltage

Page 39

InRow RD Technical Data Manual36Bottom piping and power access locations (ACRD100 series and ACRD200 series)Dimensions are shown in mm (in).Electrica

Page 40

37InRow RD Technical Data ManualTop piping and power access locations (ACRD500 series)Dimensions are shown in mm (in).Refrigerant discharge lineRefr

Page 41 - Note: Bottom piping shown

InRow RD Technical Data Manual38Bottom piping and power access locations (ACRD500 series)Dimensions are shown in mm (in).Refrigerant liquid lineRefr

Page 42

39InRow RD Technical Data ManualOutdoor Heat ExchangersAir Cooled Condensers - Mechanical Data (ACRD100 Series)SKUAmbient Tem p°C (°F)Sound Pressure (

Page 43

InRow RD Technical Data Manual40Air Cooled Condensers - Electrical Data (ACRD100 Series)SKU Voltage Phase Frequency FLA MCA MOPACCD75214 208-240V 1 ph

Page 44

41InRow RD Technical Data ManualACCD75201 and ACCD75204ACCD75202 and ACCD75205ACCD75203 and ACCD75206Dimensions are shown in mm (in). All co

Page 45

ContentsInRow RD Technical Data ManualiOverview ... 1Scalable Solution for Crit

Page 46

InRow RD Technical Data Manual42ACCD75207ACCD75208 and ACCD75209Dimensions are shown in mm (in). All condensers shown on this page have 16 m

Page 47 - Outdoor Heat Exchangers

43InRow RD Technical Data ManualACCD75214ACCD75215ACCD75216 and ACCD75218Dimensions are shown in mm (in).na2891ana2895ana2893a

Page 48

InRow RD Technical Data Manual44ACCD75217 and ACCD75219ACFC75210ACFC75255Dimensions are shown in mm (in).na2896ana2890ana2899a

Page 49 - ACCD75203 and ACCD75206

45InRow RD Technical Data ManualACFC75256Dimensions are shown in mm (in).ACFC75257Dimensions are shown in mm (in).Air-cooled Condenser FeaturesAvailab

Page 50 - ACCD75208 and ACCD75209

InRow RD Technical Data Manual46Guide SpecificationsPART 1 — GENERAL1.01 SUMMARYA. The environmental control system shall be designed specifically for

Page 51 - ACCD75216 and ACCD75218

47InRow RD Technical Data ManualPART 2 — PRODUCT2.01 STANDARD COMPONENTSA. Cabinet Construction1. Front and rear exterior panels shall be 18 gauge per

Page 52 - ACFC75255

InRow RD Technical Data Manual48C. Main Disconnect Switch1. The unit shall be provided with thermal-magnetic circuit breakers with interrupt capacity

Page 53 - Air-cooled Condenser Features

49InRow RD Technical Data Manualu. Internal communication faultv. On standby input contact faultw. A-link isolation relay faultx. Excessive compressor

Page 54 - Guide Specifications

InRow RD Technical Data Manual50F. Cooling Coil And Condensate Pan1. ACRD100 and ACRD200 series:a. The cooling coil shall use corrugated aluminum fin

Page 55

51InRow RD Technical Data ManualI. Filters1. ACRD100 series and ACRD200 series:a. The standard filters shall be 20% efficient per ASHRAE 52.1, MERV 1

Page 56 - 460-480V 60Hz 22

InRow RD Technical Data ManualiiInRow RD Models ... 9Exterior components: ACRD100 and ACRD200

Page 57

InRow RD Technical Data Manual52N. Bridge Data Partition1. An overhead cable distribution, that sits between adjacent NetShelter racks and allows for

Page 58

53InRow RD Technical Data ManualGuidelines for InstallationThe InRow RD provides reliable, accurate temperature control of computer rooms, laboratorie

Page 59

InRow RD Technical Data Manual54Condensate drainCondensation from the evaporator pan is collected and discharged by the condensate pump to a condensat

Page 61 - Guidelines for Installation

09/2008990-3236B-001*990-3236B-001*APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any o

Page 62 - Condensate drain

InRow RD Technical Data ManualiiiPiping and Mechanical Connections ...32Refrigeration Piping Diagram (ACRD100 and ACRD500 seri

Page 63

InRow RD Technical Data ManualivSKU Selection Width Voltage Plug TypeACRD100 300 mm208-240V60 Hz 1 phHard wiredACRD101 300 mm220–240V50 Hz 1 phHard wi

Page 64 - *990-3236B-001*

1InRow RD Technical Data ManualOverviewThe modular, row-based computer room cooling system offers efficient, predictable, and economical cooling for a