Page 1 10/05/09 APC by Schneider Electric MGE GALAXY 3500 Uninterruptible Power Supply Guide Specifications 10-30 kVA Three-Phase, 208 Volts, 60 H
Page 10 10/05/09 1A/1B auxiliary contacts. The circuit breakers shall be equipped as part of a line-up-and-match type battery enclosure. B. Mai
Page 11 10/05/09 c. Sufficient APC CAN bus PCB’s to provide adequate communications of the PSMBC status to the UPS system parallel control system
Page 12 10/05/09 A. General: Preparation and installation shall be in accordance with reviewed product data, final shop drawings, manufacturer’
Page 13 10/05/09 1. Test and adjust controls and safeties. Replace damaged or malfunctioning controls and equipment. 2. Train the Owner’s maint
Page 2 10/05/09 referenced publications shall be the latest date as of the date of the Contract Documents, unless otherwise specified. B. Instit
Page 3 10/05/09 g. Overload Rating: 1) Normal Operation: a) 150 percent for 1 minute. b) 125 percent for 10 minutes. c) 100 percent continuou
Page 4 10/05/09 B. Regulatory Requirements: Comply with applicable requirements of the laws, codes, ordinances, and regulations of Federal, Stat
Page 5 10/05/09 indicated below. This special warranty shall extend the one year period of limitations contained in the General Conditions. The
Page 6 10/05/09 and service of the UPS. The MBC shall completely isolate both the UPS input and output connections. The MBC shall be used for pa
Page 7 10/05/09 the outlined time limitation; the critical load shall be switched to the automatic static bypass output of the UPS. C. Output Co
Page 8 10/05/09 2. Source input voltage. 3. Output AC voltage. 4. Output AC current. 5. Input frequency. 6. Battery voltage. 7. Highest intern
Page 9 10/05/09 1. Indicating LED’s: a. Load On: When green, this LED shall indicate the load is being supported by the UPS output. b. On Batt