MGE GALAXY 3500
Uninterruptible Power Supply
Guide Specifications
10-30 kVA
Three-Phase, 208 Volts, 60 Hertz Solution
THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI)
MASTERFORMAT. THIS SECTION MUST BE CAREFULLY REVIEWED AND EDITED BY THE ARCHITECT OR THE ENGINEER TO
MEET THE REQUIREMENTS OF THE PROJECT. COORDINATE THIS SECTION WITH OTHER SPECIFICATION SECTIONS IN
THE PROJECT MANUAL AND WITH THE DRAWINGS.
WHERE REFERENCE IS MADE THROUGHOUT THIS SECTION TO “PROVIDE”, “INSTALL”, “SUBMIT”, ETC., IT SHALL MEAN
THAT THE CONTRACTOR, SUBCONTRACTOR, OR CONTRACTOR OF LOWER TIER SHALL “PROVIDE”, “INSTALL”, SUBMIT”,
ETC., UNLESS OTHERWISE INDICATED.
THIS SECTION IS WRITTEN TO INCLUDE THE 2004 MASTERFORMAT AND THE 1995 MASTERFORMAT VERSIONS. WHERE
APPLICABLE, THESE ITEMS ARE BRACKETED AND, IN EACH CASE, UNLESS OTHERWISE INDICATED, THE FIRST CHOICE
APPLIES TO THE 2004 MASTERFORMAT AND THE SECOND CHOICE APPLIES TO THE 1995 MASTERFORMAT.
SECTION [26 33 63.17] [16611-11]
SOLID STATE UNINTERRUPTIBLE POWER SUPPLY
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General Conditions,
[Division 01 - GENERAL REQUIREMENTS] [Division 1 - GENERAL REQUIREMENTS], and other
applicable specification sections in the Project Manual apply to the work specified in this Section.
1.2 SUMMARY
A. Scope: Provide design and engineering, labor, material, equipment, related services, and
supervision required, including, but not limited to, manufacturing, fabrication, erection, and
installation for a solid state uninterruptible power supply (UPS) as required for the complete
performance of the work, and as shown on the Drawings and as herein specified.
B. Section Includes: The work specified in this Section includes, but shall not be limited to, a
three-phase, continuous duty, solid state UPS. The UPS shall contain a full rated input
rectifier/boost converter (hereafter referred to as input converter), output inverter, and 10 percent
battery charging circuit. The system shall also contain a continuous duty bypass static switch,
internal mechanical bypass, removable hot swap battery plant, and LCD interface display. All of the
above system components shall be housed in a single enclosure.
1. In addition, this Section describes the performance, functionality, and design of the UPS
maintenance bypass cabinet (MBC), the extended run (XR) battery system, connectivity
solutions, and paralleling operation.
2. The UPS and associated equipment shall operate in conjunction with a primary power supply
and an output distribution system to provide quality uninterrupted power for mission critical,
electronic equipment load.
3. All programming and miscellaneous components for a fully operational system as described in
this Section shall be available as part of the UPS.
1.3 REFERENCES
A. General: The publications listed below form a part of this Specification to the extent referenced.
The publications are referred to in the text by the basic designation only. The edition/revision of the
Page view 0
1 2 3 4 5 6 ... 12 13

Summary of Contents

Page 1 - APC by Schneider Electric

Page 1 10/05/09 APC by Schneider Electric MGE GALAXY 3500 Uninterruptible Power Supply Guide Specifications 10-30 kVA Three-Phase, 208 Volts, 60 H

Page 2 - Page 2 10/05/09

Page 10 10/05/09 1A/1B auxiliary contacts. The circuit breakers shall be equipped as part of a line-up-and-match type battery enclosure. B. Mai

Page 3 - Page 3 10/05/09

Page 11 10/05/09 c. Sufficient APC CAN bus PCB’s to provide adequate communications of the PSMBC status to the UPS system parallel control system

Page 4 - Page 4 10/05/09

Page 12 10/05/09 A. General: Preparation and installation shall be in accordance with reviewed product data, final shop drawings, manufacturer’

Page 5 - Page 5 10/05/09

Page 13 10/05/09 1. Test and adjust controls and safeties. Replace damaged or malfunctioning controls and equipment. 2. Train the Owner’s maint

Page 6 - Page 6 10/05/09

Page 2 10/05/09 referenced publications shall be the latest date as of the date of the Contract Documents, unless otherwise specified. B. Instit

Page 7 - Page 7 10/05/09

Page 3 10/05/09 g. Overload Rating: 1) Normal Operation: a) 150 percent for 1 minute. b) 125 percent for 10 minutes. c) 100 percent continuou

Page 8 - Page 8 10/05/09

Page 4 10/05/09 B. Regulatory Requirements: Comply with applicable requirements of the laws, codes, ordinances, and regulations of Federal, Stat

Page 9 - Page 9 10/05/09

Page 5 10/05/09 indicated below. This special warranty shall extend the one year period of limitations contained in the General Conditions. The

Page 10 - Page 10 10/05/09

Page 6 10/05/09 and service of the UPS. The MBC shall completely isolate both the UPS input and output connections. The MBC shall be used for pa

Page 11 - Page 11 10/05/09

Page 7 10/05/09 the outlined time limitation; the critical load shall be switched to the automatic static bypass output of the UPS. C. Output Co

Page 12 - Page 12 10/05/09

Page 8 10/05/09 2. Source input voltage. 3. Output AC voltage. 4. Output AC current. 5. Input frequency. 6. Battery voltage. 7. Highest intern

Page 13 - Page 13 10/05/09

Page 9 10/05/09 1. Indicating LED’s: a. Load On: When green, this LED shall indicate the load is being supported by the UPS output. b. On Batt

Comments to this Manuals

No comments