APC PX 48 kW 400 V UPS PX 96 kW 400 V UPS PX 160 kW 400 V UPS PX 100 kW 208 V UPS Specifications

Browse online or download Specifications for Networking APC PX 48 kW 400 V UPS PX 96 kW 400 V UPS PX 160 kW 400 V UPS PX 100 kW 208 V UPS. APC PX 48 kW 400 V UPS PX 96 kW 400 V UPS PX 160 kW 400 V UPS PX 100 kW 208 V UPS Specifications User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Operation

OperationSymmetra™PX48,96,and160kW400V100kW208Vtest

Page 2 - LegalDisclaimer

Caution:Thedisplayprovidesaccesstomorefunctionsthandescribedinthismanual.ThosefunctionsshouldnotbeaccessedwithouttheassistanceofSchneiderElectricCusto

Page 3

OperationModesInaninstallationthatdoesnotincludeamaintenancebypasspanel,theUPShasthreeoperationmodes:normaloperation,batteryoperationandstaticbypassop

Page 4

PerformaTotalPowerOffWARNING:Thisprocedurewilldisconnecttheload.Note:Ifshutdownviathedisplayisdisabled,thenyoucannotperformthisprocedureandthemessage:

Page 5 - AboutthisManual

7.SettheUPSSYSTEMENABLEswitchtotheOFFposition.8.SettheQ2switchtotheOFFposition.9.SettheQ1switchtotheOFFposition.10.SettheQ5breakertotheOFFposition(ifa

Page 6 - Overview

StarttheSystemafterTotalPowerOff1.Settheupstreamutility/mainspowertotheONorLOCKEDINposition.IftheUPShasadualmainssupply,setbothsuppliestotheONorLOCKED

Page 7 - DisplayInterface

10.ConrmbyselectingY es,TurnUPSOnandpressENTER.Confirm:TurnUPSOn?>NO,ABORT→>Yes,TurnUPSOn11.WaitfortheUPStoturnon.TurningUPSon,Pleasewait...990

Page 8 - MainMenuScreen

TurntheUPSLoadOff1.SelectUPSandpressENTER.→UPSAlarmsPowerDistLogSwitchGearAdminEnvironmentHelp2.SelectUPSPowerControlandpressENTER.→UPSPowerControlUPS

Page 9 - MenuTree

TurntheUPSLoadOn1.SelectUPSandpressENTER.→UPSAlarmsPowerDistLogSwitchGearAdminEnvironmentHelpPress2.SelectUPSPowerControlandpressENTER.→UPSPowerContro

Page 10 - 990–3015E-001

TransfertheUPSintoMaintenanceBypassOperationNote:Ifshutdownviathedisplayisdisabled,thenyoucannotperformthisprocedureandthemessage:Commandnotallowed,UP

Page 11

9.SelectUPSandpressENTER.→UPSAlarmsPowerDistLogSwitchGearAdminEnvironmentHelp10.SelectUPSPowerControlandpressENTER.→UPSPowerControlUPSStatusUPSTests&a

Page 12 - PerformaTotalPowerOff

LegalDisclaimerTheinformationpresentedinthismanualisnotwarrantedbytheSchneiderElectricITCorporationtobeauthoritative,errorfree,orcomplete.Thispublicat

Page 13

PDUXR(ifapplicable)andonthemainframe(onlyPX48).ReturntoNormalOperationfromMaintenanceBypassOperation1.SettheDCDISCONNECTswitchtotheONpositiononallXRBa

Page 14

8.SelectTurnUPSOnintoBypassandpressENTER.TurnUPSOn→UPSOnintoBypass9.SelectContinueTurnOnandpressENTER.Batteryback-upnotavailableinbypass!>Cancel→&g

Page 15 - 11.WaitfortheUPStoturnon

18.SelectUPSoutofBypassandpressENTER.TurnUPSOffRebootUPS→UPSoutofBypassUPStoSleep19.ConrmbyselectingYes,OutofBypassandpressENTER.Confirm:UPSoutofBypa

Page 16 - TurntheUPSLoadOff

ViewtheStatusScreens1.SelectUPSandpressENTER.→UPSAlarmsPowerDistLogSwitchGearAdminEnvironmentHelp2.SelectUPSStatusandpressENTER.UPSPowerControl→UPSSta

Page 17 - TurntheUPSLoadOn

CongurationSystemSettingsSetUptheNetwork1.SelectAdminandpressENTER.UPSAlarmsPowerDistLogSwitchGear→AdminEnvironmentHelp2.SelectNetworkSetupandpressEN

Page 18

ChangetheDisplayInterfaceSettings1.SelectAdminandpressENTER.UPSAlarmsPowerDistLogSwitchGear→AdminEnvironmentHelp2.SelectLocalInterfaceandpressENTER.Ne

Page 19

ChangetheDateandTime1.SelectAdminandpressENTER.UPSAlarmsPowerDistLogSwitchGear→AdminEnvironmentHelp2.SelectDate/TimeandpressENTER.NetworkSetupLocalInt

Page 20

CongureOutputRelays1.SelectEnvironmentandpressENTER.UPSAlarmsPowerDistLogSwitchGearAdmin→EnvironmentHelp2.SelectOutputRelaysandpressENTER.InputContac

Page 21

MaintenanceLifeCycleMonitoring(LCM)TheLifeCycleMonitoring(LCM)functionprovidesUPSmaintenanceadvicetoguaranteeinstallationavailabilityfortheuser.Thedis

Page 22

ToreturnafailedmoduletoSchneiderElectric,packthemoduleintheoriginalshippingmaterials,andreturnitbyinsured,prepaidcarrier.TheSchneiderElectricCustomerS

Page 23 - ViewtheLogScreen

TableofContentsAboutthisManual...1CompanionManu

Page 24 - Conguration

ReplacementPartsWARNING:AllsafetyinstructionsintheSafetysheet(990-2984)shouldberead,understood,andfollowedpriortohandlingthesystem.Failuretodosocouldr

Page 25 - 1.SelectAdminandpressENTER

ReplaceaPowerModuleWARNING:Beforeremovinganypowermodules,makesurethattheremainingpowermodulescansupporttheload.WARNING:Twopeopleareneededtoliftcompone

Page 26 - CongureInputContacts

ReplaceaBatteryWARNING:Servicingofbatteriesshouldbeperformedorsupervisedbypersonnelknowledgeableaboutbatteriesandtherequiredprecautions.Caution:Whenre

Page 27 - CongureOutputRelays

Storageofthebatterymodules:Thebatterymodulesmustbestoredindoorsandwiththeirprotectivepackagingstillinplace.Ambienttemperature:-15to40°C(5to104°F)Relat

Page 28 - Maintenance

Note:Whenreplacingbatteries,alwaysreplacebothbatteriesA+BorC+D(seeillustrationabove)astheyareinterconnectedinpairs.Forfourbatteriesinarowitisrecommend

Page 29

ReplaceaPowerDistributionModuleNote:Theloadthatisconnectedtotheactualpowerdistributionmodulewillnotbesupportedwhenthelockinglatchonthemoduleisopened.1

Page 30 - ReplaceaPowerManagementCard

TroubleshootingWARNING:Onlytrainedpersonsfamiliarwiththeconstructionandoperationoftheequipment,aswellastheelectricalandmechanicalhazardsinvolved,mayin

Page 31 - ReplaceaPowerModule

DisplayMessageMeaningCorrectiveActionExtendedRunFrameFaultOneofthebatteryenclosureshasfailed.ContactSchneiderElectricCustomerSupport(seethebackcover).

Page 32 - ReplaceaBattery

DisplayMessageMeaningCorrectiveActionNoPowerModulesDetectedNopowermodulesareavailable.Option1:Ensurethatthepowermodulesareproperlyinstalled,thetwofast

Page 33

DisplayMessageMeaningCorrectiveActionStaticBypassSwitchModuleRemovedThesystemnolongerdetectsastaticbypassswitchmodule.Option1:Ensurethatthestaticbypas

Page 34

Troubleshooting...32StatusandAlarmMessages.

Page 35

ModularDistributionFaultListThedisplayinterfacewillidentifythenumberofthepowerdistributionmodulesthathascausedanalarmorwarning.DisplayMessageMeaningCo

Page 36

PDUFaultListDisplayMessageMeaningCorrectiveActionSystemInMaintenanceBypassThesystemisinmaintenancebypass:theQ2switchisopenandtheQ3switchisclosed.Nocor

Page 39

WorldwideCustomerSupportCustomersupportisavailableatnochargeviae-mailortelephone.Contactinformationisavailableatwww.apc.com/support/contact©SchneiderE

Page 40

AboutthisManualThismanualisfor:•SymmetraPX48kW400VUPS•SymmetraPX96and160kW400VUPSandPowerDistributionUnit(PDU-XR)•SymmetraPX100kW208VUPSandPowerDistri

Page 41 - PDUFaultList

OverviewUserInterfaceALOADPOWEREDLEDWhenthisLEDisgreen,powertotheloadison.WhentheLEDisyellow,theloadissuppliedthroughthebatteries.WhentheLEDisashingy

Page 42

DisplayInterfaceOverviewScreensTheOverviewScreenisthemainentrancetotheuserfunctionsofthedisplayinterface.TheUP/DOWNnavigationkeystakeyoufromonescreent

Page 43

MainMenuScreenFromthemainmenuitispossibletocongureandmonitorthesystemthroughthesubmenuscreens:UPS,PowerDist,Switchgear,Environment,Alarms,Log,Admin,a

Page 44 - WorldwideCustomerSupport

MenuTreeThemenutreeprovidesaquickoverviewofthefunctionsandviewsyoumayaccess.UPSPowerControlUPSUPSStatusUPSTests&DiagsUPSCongurationTotalLoadingPo