All content in this presentation is protected – © 2008 American Power Conversion CorporationAPC 3Phase Power DistributionNorth American 3 Phase Busine
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 High Efficiency AC vs. DC Power Distribution - WP 127Overall Power Path Efficiency Compa
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 Higher Voltage AC Power Distribution - WP 128UPSPDU(s)120 / 208 V120 / 208 V120 / 208 V2
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 Single Phase Voltages● Servers draw their power from the 208 V high voltage (line to lin
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 Scalable, Reconfigurable, Efficient Power Distribution - WP 129
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 Modular Products and HACSAN-151
All content in this presentation is protected – © 2008 American Power Conversion CorporationSite Considerations
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 415V Site Considerations● Any 480V output UPS with a 5 wire output can feed the Modular
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 208V Modular RPP site considerations● What Can I Feed From These Units? ● ISX 80•PDPM144
All content in this presentation is protected – © 2008 American Power Conversion CorporationBackup Slides
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 InfraStruXure™Modular Power DistributionDistribution Modules•20A IEC309 3PH Female•20A I
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 Objectives● Understand the entire 3Phase power Distribution portfolio to include:● Infra
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 InfraStruXure™208VModular Power Distribution● Enclosure - 300mm 144kW Remote Power Panel
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 3-Phase Power DistributionManagement OptionsRow Based Power Distribution Row Based Modul
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 415V NAM Data Center ApplicationsOption 1 - Rack PDU● 20A Breaker Module with 1 IEC309 3
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 415V NAM Data Center ApplicationsOption 2 - 200V In Row RC● 20A Breaker Module with 3 IE
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 415V NAM Data Center ApplicationsOption 3 - Directly Connect 240V Servers● 20A Breaker M
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 415V NAM Data Center ApplicationsOption 4 - Calamari to 1U Rack PDU● 20A Breaker Module
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 Technical SpecificationsYesYesPanelboard Main Circuit BreakerNoYes200% Rated Neutral Bus
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 Options/AccessoriesYesNoShunt TripNoYesRemote EPOYesYesInput Junction BoxNoYesManual Res
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 APC 3 Phase Power Distribution PortfolioISX Row-basedISX ModularRoom-based600,480,208V,
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 InfraStruXure™Modular Power Distribution● Safely expand and service without forced shutd
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 InfraStruXure™Row-based Power Distribution● Included Monitoring enables standard SNMP in
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 Room-based Power Distribution ● Integrated isolation with electronic grade grounding, an
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 Room- Based Power DistributionUPSPMM RPMMRPMM
APC by Schneider Electric – Mark Tarantelli – 4 November 2008 3 Phase Power Distribution Positioning● Modular● Hot Swap PDMs● Safety without forced Sh
All content in this presentation is protected – © 2008 American Power Conversion CorporationSales Tools