Uninterruptible Power Supply
Guide Specifications
1 kVA, 2 kVA, 2.2 kVA, 3 kVA, 5 kVA, 6 kVA, 8 kVA, 10 kVA, 15 kVA, and 20 kVA,
230 V Solution
THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE
(CSI) MASTERFORMAT. THIS SECTION MUST BE CAREFULLY REVIEWED AND EDITED BY THE ARCHITECT OR THE
ENGINEER TO MEET THE REQUIREMENTS OF THE PROJECT. COORDINATE THIS SECTION WITH OTHER
SPECIFICATION SECTIONS IN THE PROJECT MANUAL AND WITH THE DRAWINGS.
WHERE REFERENCE IS MADE THROUGHOUT THIS SECTION TO “PROVIDE”, “INSTALL”, “SUBMIT”, ETC., IT SHALL MEAN
THAT THE CONTRACTOR, SUBCONTRACTOR, OR CONTRACTOR OF LOWER TIER SHALL “PROVIDE”, “INSTALL”,
SUBMIT”, ETC., UNLESS OTHERWISE INDICATED.
SOLID STATE UNINTERRUPTIBLE POWER SUPPLY
PART 1 - GENERAL
1.1 SUMMARY
A. Scope: This specification describes the operation and functionality of a continuous
duty, single-phase, solid-state, static Uninterruptible Power Supply (UPS) hereafter
referred to as the UPS.
B. Included Features of the UPS:
1. The UPS utilizes double conversion online topology designed to protect electronic
equipment by supplying reliable, network-grade power featuring extremely tight
voltage and frequency regulation.
2. The UPS features internal bypass and input power factor correction.
3. The primary sections of the UPS are: input disconnect and filter stage, input PFC
power stage, energy storage stage (DC bus capacitor bank), output power
(inverter) stage, bypass, and a battery charger. The control of power module and
fault detection logic is microcontroller-based.
a. The input disconnect and filter stage contains an input back-feed relay (in
models with an input wire plug), input filter, transient suppression, and battery
select switches (mechanical relay or solid-state).
b. The Input PFC power stage contains non-isolated power-factor-correcting
AC/DC converters. These converters are capable of full power operation in a
very wide input voltage range or from a nominal DC battery voltage.
c. The energy storage stage is a split DC bus capacitor handling seamless
transitions from battery to online and vice versa as well as the low and high
frequency power stages ripple.
d. The output power (inverter) stage operates directly from the DC bus and
produces a configurable AC output voltage of 200, 208, 220, 230 or 240 Vac
output, 1 kVA and 2 kVA models produce 220, 225, 230 or 240 Vac, 15 kVA
and 20 kVA models produce 220, 230, 240 Vac (single phase) or 380, 400,
415 Vac (three phase). The output of the UPS is connected either to the
inverter or through a bypass relay or static switch to the filtered input line.
e. The UPS contains a battery charger, which operates from the DC bus. The
UPS batteries are modular, hot-swappable, and user-replaceable.
C. Performance, Design, and Configurations: The UPS and associated equipment
operates in conjunction with a primary power supply and an output distribution system to
provide quality uninterrupted power for a mission-critical, electronic equipment load.
1. This specification describes the performance, functionality, and design of the UPS
Service Bypass Panel, hereafter referred to as the SBP, the external Battery
Systems, and connectivity solutions.
2. All programming and miscellaneous components for a fully operational system as
described in this specification are available as part of the UPS.
Page view 0
1 2 3 4 5 6 ... 12 13

Summary of Contents

Page 1 - APC by Schneider Electric

Page 1 APC by Schneider Electric Smart-UPS RT Uninterruptible Power Supply Guide Specifications 1 kVA, 2 kVA, 2.2 kVA, 3 kVA, 5 kVA, 6 kVA, 8 kVA

Page 2 - Page 2

Page 10 2.5 DISPLAY AND CONTROLS A. Control Logic: The UPS is controlled by an embedded microcontroller which performs the following funct

Page 3 - Approvals

Page 11 G. Potential Free (Dry) Contacts: The following potential free contacts are available on an optional APC SmartSlot Relay I/O Card (Not a

Page 4 - Page 4

Page 12 b. Rack-Mount models: APC Smart-UPS RT 2200 VA 230 V – Marine SURTD2200XLIM), APC Smart-UPS RT 3000 VA RM 230 V (SURTD3000RMXLI), APC Sm

Page 5 - Page 5

Page 13 3. Verify proper firmware bypass operation. 4. Verify proper bypass switch operation (where applicable). 5. Verify proper inverter ope

Page 6 - Page 6

Page 2 3. The UPS is available in the following configurations: TYPE MODEL SKU Tower APC Smart-UPS RT 1000 VA RM 230 V SURT1000XLI APC Smar

Page 7 - Page 7

Page 3 1.3 STANDARDS A. Regulatory Compliance: 1. By model: Model SKU Approvals APC Smart-UPS RT 1000 VA RM 230 V SURT1000RMXLI C-tick, C

Page 8 - Page 8

Page 4 2. OSHPD Pre-approval: In addition to the preceding regulatory approvals, the APC Smart-UPS RT 3 kVA RM 230 V model (SURTD3000RMXLI) and

Page 9 - Page 9

Page 5 c. 2.2 kVA or 1540 W, whichever limit is reached first (for the 2.2 kVA model). d. 3 kVA or 2100 W, whichever limit is reached first (fo

Page 10 - Page 10

Page 6 d. AC output voltage distortion: 1) Maximum 3% @ 100% linear load; maximum 8% @ 100% non-linear (1 kVA and 2 kVA models) 2) Maximum 2%

Page 11 - Page 11

Page 7 ceilings is complete, and ambient temperature and humidity conditions are and will be continuously maintained at values near those indicat

Page 12 - Page 12

Page 8 2.2 MODES OF OPERATION A. Normal: The UPS output power stage (inverter) constantly recreates the UPS output voltage waveform by con

Page 13 - Page 13

Page 9 1. Automatic Transfers: An automatic transfer of load to bypass takes place whenever the load on the critical bus exceeds the overload r