Page 1 APC by Schneider Electric Smart-UPS RT Uninterruptible Power Supply Guide Specifications 1 kVA, 2 kVA, 2.2 kVA, 3 kVA, 5 kVA, 6 kVA, 8 kVA
Page 10 2.5 DISPLAY AND CONTROLS A. Control Logic: The UPS is controlled by an embedded microcontroller which performs the following funct
Page 11 G. Potential Free (Dry) Contacts: The following potential free contacts are available on an optional APC SmartSlot Relay I/O Card (Not a
Page 12 b. Rack-Mount models: APC Smart-UPS RT 2200 VA 230 V – Marine SURTD2200XLIM), APC Smart-UPS RT 3000 VA RM 230 V (SURTD3000RMXLI), APC Sm
Page 13 3. Verify proper firmware bypass operation. 4. Verify proper bypass switch operation (where applicable). 5. Verify proper inverter ope
Page 2 3. The UPS is available in the following configurations: TYPE MODEL SKU Tower APC Smart-UPS RT 1000 VA RM 230 V SURT1000XLI APC Smar
Page 3 1.3 STANDARDS A. Regulatory Compliance: 1. By model: Model SKU Approvals APC Smart-UPS RT 1000 VA RM 230 V SURT1000RMXLI C-tick, C
Page 4 2. OSHPD Pre-approval: In addition to the preceding regulatory approvals, the APC Smart-UPS RT 3 kVA RM 230 V model (SURTD3000RMXLI) and
Page 5 c. 2.2 kVA or 1540 W, whichever limit is reached first (for the 2.2 kVA model). d. 3 kVA or 2100 W, whichever limit is reached first (fo
Page 6 d. AC output voltage distortion: 1) Maximum 3% @ 100% linear load; maximum 8% @ 100% non-linear (1 kVA and 2 kVA models) 2) Maximum 2%
Page 7 ceilings is complete, and ambient temperature and humidity conditions are and will be continuously maintained at values near those indicat
Page 8 2.2 MODES OF OPERATION A. Normal: The UPS output power stage (inverter) constantly recreates the UPS output voltage waveform by con
Page 9 1. Automatic Transfers: An automatic transfer of load to bypass takes place whenever the load on the critical bus exceeds the overload r