990-1022, Revision 1 5/00User’s ManualEnglishAPC Smart-UPS2U Rack and StackExternal Battery Pack
6Place The Battery Pack Where It Will Be UsedThe battery pack requires two people to install due to its weight.To lighten the battery pack, you may re
7To Mount the Battery Pack in a RackThe battery pack comes with standard 19-inch (46.5 cm) rack mount brackets (in the literature kit)and mounting rai
8Attach the Mounting Brackets to the Battery Pack• Each mounting bracket attaches to the battery pack with four (4) screws, included.• Two sets of b
9Slide the Battery Pack in the RackDue to the weight of the battery pack, two people are required to install it in the rack.1. Using the handles on
10Connect the Battery Pack(s) to the Smart-UPSBattery pack connectors are color coded and keyed to prevent improperconnection. The color of the conne
11CHAPTER 4: OPERATING THE SMART-UPSConnectors on the Battery PackThe front panel of the battery pack contains a simple bezel (for identification). T
12How to Set the Smart-UPS to Recognize the Battery Pack(s)Smart-UPS XL models cannot determine how many external battery packs are connected to them.
13Use the Terminal Program to Change the Number of External Battery PacksTerminal is used in Windows 3.1x, Windows for Workgroups, and Windows NT 3.51
14Use the HyperTerminal Program to Change the Number of External Battery PacksHyperTerminal is used for Windows 95, Windows 98, and Windows NT 4.01.
15CHAPTER 5: MAINTENANCE AND TROUBLESHOOTINGStorageStorage ConditionsStore the battery pack covered and flat (rack mount orientation) in a cool, dry
990-1022, Revision 1 5/00Entire contents copyright © 2000 by American Power Conversion Corporation. All rightsreserved. Reproduction in whole or in
161. Face the front of the battery pack and, using both hands,insert each index finger behind the lip of the curvedsection of the front bezel and pul
17ServiceIf the battery pack requires service do not return it to the dealer!Follow these steps:1. Verify that no circuit breakers are tripped. A tr
19APPENDIX A: SPECIFICATIONS2U Battery Pack (SU24RMXLBP2U)Battery type Spill proof, maintenance free, sealed lead-acidTypical battery life 3 – 6 year
990-1022, Revision 1 5/00Table of ContentsChapter 1: Safety Information...1Conventions Us
1CHAPTER 1: SAFETY INFORMATIONThis Safety Guide contains important instructions that should be followed during the installationand maintenance of the
2Electrical Safety• To reduce the risk of fire, connect only to a circuit provided with a 20 Amp maximum branchcircuit overcurrent protection in acco
3CHAPTER 2: BASICSAbout Your Battery PackThis APC 2U Rack and Stack Battery Pack is designed to connect to an APC UninterruptiblePower Supply (UPS) t
4How To Contact APCInternethttp://www.apcc.com/contactNorth AmericaPhone 1.800.800.4272Fax 1.401.788.2743Latin AmericaArgentina 0800.9.APCC (0800.9.27
5CHAPTER 3: INSTALLING YOUR BATTERY PACKUnpackingAPC has taken care to design robust packaging for your product. However, accidents and damagemay oc