16
Specifications
Remote switch
requirements
For remote switch requirements, see “Switch types: Table
4” on page 10.
Cable
requirements
The Remote Power-Off Device comes with two
RJ11
cables. Some users may choose to use existing building
cables. The cable that connects the Remote Power-Off
Device to the remote switch must be
UL
listed,
26-22 AWG
,
and one of the following types:
•
CL2
Class 2 cable for general use
•
CL2P
Plenum cable for use in ducts, plenums, or
other space used for environmental air
• CL2R Riser cable for use in a vertical run in a shaft or
from floor to floor
• CL2X Limited-use cable for use in dwellings or in
raceway
For installations in Canada, the cable must be
CSA
certified,
type
ELC
(extra-low-voltage control cable).
Warning
Wiring safety is the responsibility of those installing the
cable. Incorrect installation can result in improper function-
ing of the device or damage to hardware. The use of
substandard cables can produce toxic fumes in the event of
a fire.