Smart-UPS
®
RT
Technical Specifications
Smart-UPS RT
1000
Smart-UPS RT
2000
Smart-UPS RT
3000
Smart-UPS RT
5000
Smart-UPS RT
7500
Smart-UPS RT
10000
Output
Capacity 1kVA/.7kW 2kVA/1.4kW 3kVA/2.1kW 5kVA/3.5kW 7.5kVA/6kW 10kVA/8kW
Output Voltage 230 (default), 220, 240 VAC (user selectable), single phase
Output Voltage Regulation (Typical) +/- 1% static, 5% dynamic
Output Connections (6) IEC C13 (8) IEC C13, (2) IEC C19 (4) IEC C13, (4) IEC C19, hardwire
output terminal block
Efficiency at Full Load, Nominal Line 87% 90% 91% 92% 92% 92%
Output Frequency (sync’d to mains) 50 or 60 Hz, +/- 3Hz (auto-select default) [or 50 or 60 Hz +/-0.1Hz (user selectable)]
Bypass Automatic Automatic/Manual
Overload Capacity 105% - infinite, 125% - 1 min, 150% - 30 seconds
Output Voltage Distortion <3% for linear loads, <5% for non-linear loads
Crest Factor 3:1
Heat Dissipation (Watts), Nominal Line 90 140 192 305 450 650
Input
Nominal Input Voltage 220, 230 (default), 240 VAC Single Ø 220, 230 (default), 240 VAC Single or Three Ø
Input Frequency 45-65 Hz Auto-selecting
Input Connection IEC C14 IEC C20 Hardwire
Input Voltage Range 160 - 280 VAC (at full load), 100 - 280 VAC (at half load)
Input Power Factor at Full Load >.95
Batteries
Battery Type Maintenance-free, Sealed Lead-Acid, valve regulated, 3-6 years typical lifetime
Recharge Time to 90% Capacity < 3 Hours < 4 Hours < 3 Hours
Communications and Management
Interface Port 1) SmartSlot accessory port; (1) Serial communication port (1) RJ-45 10/100 Base T Connection; (1) Serial Communication port
Web/SNMPManagement Card optional included
Management Software included PowerChute Business Edition for Windows NT/2000/XP,Novell Netware, PowerChute Network Shutdown for
Solaris, Linux RedHat, PowerChute plus for HP-UX and IBM AIX Windows NT/2000/XP, Novell Netware, AIX
(Smart-UPS RT 5000 also ships with PowerChute Network Shutdown) Solaris, Linux RedHat, HP-UX, IBM AIX
Physical
Dimensions HxWxD (mm and inches) 85x432x482 mm, 3.4x17x19 in 130x432x660 mm, 5.1x17x26 in 264x432x663 mm, 10.4x17x26.12 in
U Height 2 3 6
Weight net/shipping (kg) 23/27.8 kg 25/29.8 54.5/64 111/129
Environmental
Operating Conditions 3,000 m max elevation; 0-95% non-condensing humidity; 0-40˚ C
Storage Conditions 15,000 m max. elevation; 0-95% non-condensing humidity; -20 to 60˚ C
Audible noise at 3 feet (1 m) < 50 dB < 55 dB
Warranty & Conformance
Approvals BSMI; C-Tick; CE; EN 50091-1; EN 50091-2; VDE; EN 55022 Class A; EN 60950; EN 61000-3-2; GOST; JEON; PCBC; UL 1778; CSA; VCCI
Warranty 2 years, repair or replace, optional on-site warranties available, optional extended warranties available
Ordering Guide
Tower UPS Part Number SURT1000XLI SURT2000XLI SURT3000XLI SURT5000XLI SURT7500XLI SURT10000XLI
Rack-mount UPS Part Number SURT1000XLI SURT2000XLI SURT3000XLI SURT5000XLI SURT7500XLI SURT10000XLI
(+) SURTRK (+) SURTRK (+) SURTRK2 (+) SURTRK2 (+) SURTRK2 (+) SURTRK2
Tower Battery Pack Part Number SURT48XLBP SURT192XLBP
Rack-mount Battery Pack Part Number SURT48XLBP (+) SURTRK SURT192XLBP (+) SURTRK2
Replacement Battery Cartridge RBC31 RBC31 RBC44 RBC44 2x RBC44 2x RBC44
Battery Packs
Models Net Weight (kg) Ship Weight (kg) Rack Height Max Dimensions Ship Dimensions (mm/in) For Use With: RBC
SURT48XLBP 29.6 32.3 2U 85 x 432 x 483 287 x 630 x 595 SURT1000XLI, SURT2000XLI 2 x RBC31
3.34 x 17 x 19 11.3 x 24.8 x 23.4
SURT192XLBP 90.9 101.4 3U 130 x 432 x 660 414 x 600 x 1000 SURT3000XLI, SURT5000XLI 2 x RBC44
5.1 x 17 x 26 16.3 x 23.6 x 39.4 SURT7500XLI, SURT10000XLI
For more information about APC products go to www.apc.com