APC MGE Galaxy 300 User's Guide Page 34

  • Download
  • Add to my manuals
  • Print
  • Page
    / 105
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 33
Network Management Card User’s Guide25
uio
Access: Administrator, Device User
Description: This command is available for an AP9631 and AP9635 Network Management Card with a
connected Dry Contact I/O Accessory (AP9810).
Example 1: To open the output, type:
uio -rc 2 open
Example 2: To view the status of the devices connected to a Dry Contact I/O Accessory that is installed in
universal input/ output port 2, type:
uio -st 2
ups
|
Note: Command is only available on the MGE Galaxy 300 and MGE Galaxy 7000 UPS.
Some options may only be available based on the individual UPS model.
Access: Administrator, Device User
Description: View UPS status information.
Option Argument Description
-rc <UIO port #> open | close Change the state of a connected output, and specify the UIO
(universal input/ output) port number.
-st
<UIO port #> |
<UIO port #>,
<UIO port #> |
<UIO port #>–<UIO port #>
View the status of the sensors connected to the Dry Contact
I/O Accessory. To view the status of a specific sensor or
several sensors, type their UIO port numbers.
-disc
<UIO port #> |
<UIO port #>,
<UIO port #> |
<UIO port #>–<UIO port #>
Identify new input contact or output relay connections.
Option Argument Description
-input <phase#> | all Display the input measurements for the chosen phase of the UPS.
Typing “all” displays the information for all phases of the UPS.
voltage | current |
frequency | all
Specify the input measurement for the ups command.
Example: ups -input 2 frequency
Displays the frequency for phase 2 of the UPS.
-bypass <phase#> | all Display the input measurements for the chosen phase of the bypass
main. Typing “all” displays all phases of the bypass main.
voltage | current |
frequency | all
Specify the input measurement for the ups command.
Example: ups -bypass 2 current
Displays the current for phase 2 of the bypass main.
Page view 33
1 2 ... 29 30 31 32 33 34 35 36 37 38 39 ... 104 105

Comments to this Manuals

No comments