Network Management Card User’s Guide35
PowerChute Network Shutdown configuration parameters
Note: By default, the PowerChute clients initiate a graceful shutdown when the UPS has 120
seconds of runtime remaining. If the servers need additional time to shut down safely,
configure the Low battery alarm threshold setting at the user interface display of the
Symmetra PX 250 or Symmetra PX 500 UPS. From the UPS System screen on the user
interface display, select User Configuration, then Alarm Settings. The valid range for the
Low battery alarm threshold is 0 (no shutdown will occur) to 3600 seconds (1 hour).
For MGE Galaxy models, you must use the UPS Tuner to set the shutdown time.
Parameter Description
Maximum Required
Delay
Displays the delay required to ensure that each PowerChute client has enough time
to shut down safely when the UPS or the PowerChute client initiates a graceful
shutdown.
When Force Negotiation is selected, the Network Management Card polls each
server listed as a PowerChute Network Shutdown client for information on the time
it needs for a graceful shutdown. This delay is recalculated whenever the
management interface of the UPS turns on or is reset. (This option is not available
for the Galaxy 300 or Galaxy 7000 UPS devices.)
Maximum Required Delay
is the longest shutdown delay needed by any server on
the list, plus two additional minutes to allow for unforeseen circumstances. The
negotiation can take up to 10 minutes.
If you do not select Force Negotiation, two minutes is used by default as the
shutdown delay for all clients.
On-Battery Shutdown
Behavior
After the PowerChute Network Shutdown clients shut down their computer
systems, this parameter determines whether the UPS turns on automatically or must
be turned on manually when input power is restored.
Note: This option is not available on the MGE Galaxy 300 or MGE Galaxy 7000
UPS.
Authentication Phrase The case-sensitive phrase of 15 to 32 ASCII characters to be used during MD5
authentication for PowerChute communication. The default Administrator setting is
admin user phrase.