38UPS Network Management Card 2 User’s Guide
Temperature and Humidity Page
Brief status
Click Temp & Humidity on the left navigation menu to display the name, alarm status, temperature, and
humidity (if supported) for each sensor.
Detailed status and configuration
Click the name of a sensor for detailed alarm status or to configure its values:
Identification and alarm status.
Thresholds.
For each sensor, you set the same types of thresholds for temperature and (if supported)
humidity measured at the sensor.
Hysteresis. This value specifies how far past a threshold the temperature or humidity must return to
clear a threshold violation.
For Maximum and High threshold violations, the clearing point is the threshold minus the
hysteresis.
For Minimum and Low threshold violations, the clearing point is the threshold plus the hysteresis.
Increase the value for Temperature Hysteresis or Humidity Hysteresis to avoid multiple alarms if
temperature or humidity that has caused a violation then wavers slightly up and down. If the hysteresis
value is too low, such wavering can cause and clear a threshold violation repeatedly.
Parameter Description
Name A name for this sensor. Maximum: 20 characters.
Location This physical location of the sensor. Maximum: 20 characters.
Alarm
Status
One of the following is displayed:
Normal if this sensor is not reporting an alarm condition.
• If this sensor is in an alarm state, the text of the alarm, indicating which threshold is violated,
and the severity of the alarm, indicated by color (red for critical, orange for warning).
Thresholds See the next two sections for descriptions of the configurable thresholds and Hysteresis values.
Threshold Description
Maximum If the threshold for maximum temperature or for maximum humidity for the sensor is
exceeded, an alarm occurs.
High If the threshold for high temperature or for high humidity for the sensor is exceeded, an alarm
occurs.
Low If the temperature or humidity drops below its low threshold for the sensor, an alarm occurs.
Minimum If the temperature or humidity drops below its minimum threshold for the sensor, an alarm
occurs.