InstallationInRow® RP CWACRP500ACRP501ACRP502
InRow RP CW Installation2Safety Note: All work should be performed by American Power Conversion (APC®) authorized personnel only. Follow all local and
3InRow RP CW InstallationInspecting the EquipmentYour APC InRow RP air conditioner has been tested and inspected for quality assurance before shipment
InRow RP CW Installation4Model IdentificationThe model number can be found on the outside of the shipping crate and on the nameplate located inside th
5InRow RP CW InstallationComponent IdentificationInstall kit inventoryItem Description Quantity Item Description QuantityInsertion adapter 2Strain r
InRow RP CW Installation6Exterior componentsRemovable rear doorsCasterSide panel lockDoor handle and lockRemovable side panelDisplay interfaceA
7InRow RP CW InstallationInterior components (front)Electrical heater Electrical panelFanMain feed breakersFan guardUser interface connectorsHu
InRow RP CW Installation8Interior components (rear)Chilled water coilRear doorsChilled water control actuatorAir filtersChilled water three-way v
9InRow RP CW InstallationElectrical panelTransformersUser interface connectorsMain controller boardRelay boardGround lugMain circuit breaker — p
InRow RP CW Installation10Main controller boardNetwork Management CardCRAC controller single inline memory module (SIMM)Differential Pressure SIMM
11InRow RP CW InstallationPiping DiagramsNote: Top or bottom entry can be chosen individually for each type of connection, i.e. power, condensate drai
This manual is available in English on the enclosed CD.Dieses Handbuch ist in Deutsch auf der beiliegenden CD-ROM verfügbar.Deze handleiding staat in
InRow RP CW Installation12ConnectionsAll connections to and from the equipment can be made through either the top or the bottom of the equipment. All
13InRow RP CW InstallationPre-InstallationRoom preparationDuring the design of the data center, consider ease of entry for the equipment, floor loadin
InRow RP CW Installation14Service accessAn area of minimum 900 mm (36 in) of clear floor space in front of and behind the equipment is recommended for
15InRow RP CW InstallationDimensions and WeightDimensionsDimensions are shown in mm (in).WeightModel Weight of equipment, packedWeight of equipment,un
InRow RP CW Installation16Piping and Power Access LocationsTop piping and power access locations (top view)Dimensions are shown in mm (in).Chilled wa
17InRow RP CW InstallationBottom piping and power access locations (bottom view)Dimensions are shown in mm (in).Chilled water supplyChilled water re
InRow RP CW Installation18InstallationJoining the Equipment to EnclosuresJoining to NetShelter® SX enclosuresThe equipment comes with four joining bra
19InRow RP CW InstallationRemoving the Doors and PanelsRemoving the front and rear doors1. Unlock and open the door 90 degrees. 2. Unplug the ground w
InRow RP CW Installation20Removing the side panelInstalling the side panelna2315ana2316a
21InRow RP CW InstallationRemoving the electrical panel coverRemove the electrical panel cover to install the main power cable.1. Remove the five M4 s
American Power Conversion Legal DisclaimerThe information presented in this manual is not warranted by the American Power Conversion Corporation to be
InRow RP CW Installation22Leveling the EquipmentNote: The leveling feet at the corners of the equipment provide a stable base if the floor is uneven,
23InRow RP CW InstallationMechanical ConnectionsTop water pipingNote: The top chilled water supply pipe is supplied with the equipment and must be ins
InRow RP CW Installation24Bottom water piping1. Remove the insulation cap from the union (not shown).2. Remove the union nut , and save it for reus
25InRow RP CW InstallationHumidifierThe humidifier water supply line is routed to the unit in flexible tubing (or alternative tubing approved by local
InRow RP CW Installation26Condensate pumpThe pump is factory-wired and piped internally to the condensate drain pan and humidifier outlet. The pump ca
27InRow RP CW InstallationCondensate overflowCaution: Failing to perform the following procedure may result in condensate pan overflow and possible da
InRow RP CW Installation28Leak sensorInstall up to four optional leak sensors (AP9326) as needed.1. Connect the leak sensor to the equipment using the
29InRow RP CW InstallationFilling and Purging the UnitWhen the unit has been properly piped, begin the filling process (top piping configuration shown
InRow RP CW Installation30ChillerThree types of chillers can be connected to the unit:• APC size-matched chiller/thermal storage system• Building ch
31InRow RP CW InstallationElectrical ConnectionsThe following electrical connections are required in the field:• Controls (user interface, Network Ma
InRow RP CW Installation32User interface connectorsRack inlet temperature sensors 1, 2, 3A-Link INA-Link OUTNetwork portConsole portCustomer out
33InRow RP CW InstallationDescription of user interface connectorsItem DescriptionRack temperature sensors 1, 2, 3 Three temperature sensors which mu
InRow RP CW Installation34Modbus D1 (RXTX+) Connections for Building Management System. Wire a 150 Ohm terminator resistor (supplied) into the final
35InRow RP CW InstallationRack temperature sensorsThe rack temperature sensors control the unit airflow and ensure adequate supply of cooling air to t
InRow RP CW Installation36Water outlet temperature sensorsThere are two water outlet temperature sensors, one for top connection and one for bottom co
37InRow RP CW InstallationCommunication connectionsA-Link connections. The A-Link bus connection allows communication between equipment. Only one InRo
InRow RP CW Installation38Building Management System (BMS). The Modbus interface allows each InRow RP to communicate with the BMS. Use a three-wire ca
39InRow RP CW InstallationNetwork portThe Network port allows communication from the InRow RP to the network.Network portLAN cable (10/100 Base-T)Sw
InRow RP CW Installation40Power ConnectionsWiring configurationsElectrical Hazard: Only a licensed electrician may connect the equipment to utility po
41InRow RP CW InstallationStrain relief (ACRP502 only)Adjustable metal strain reliefs are provided. See “Install kit inventory” on page 5.1. Hook one
ContentsInRow RP CW InstallationiGeneral Information... 1Overview . . . . . . . . . . . . . . .
InRow RP CW Installation42WarrantyOne-Year Factory WarrantyThe limited warranty provided by American Power Conversion (APC®) in this Statement of Limi
43InRow RP CW InstallationIN NO EVENT SHALL APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQU
InRow RP CW Installation44Warranty ProceduresClaimsTo obtain service under the warranty, contact APC Customer Support (see the back cover of this manu
Radio Frequency InterferenceChanges or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s
04/2008990-2710B-001*990-2710B-001*APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any o
InRow RP CW InstallationiiInstallation... 18Joining the Equipment to Enclosures .
InRow RP CW InstallationiiiWarranty ...42One-Year Factory Warranty . . . . . .
1InRow RP CW InstallationGeneral InformationOverviewSave these instructionsThis manual contains important instructions that must be followed during th