T
he APC Modular Panel Product Surge Protective Devices (SPD)
are designed to provide protection at the service entrance, branch
panels or other critical locations for today’s electrical equipment.
Compliant with UL 1449 2nd Edition requirements
dated February 9, 2007.
PMF3S-A
PMF3DS-A
PMP3S-A
PMP3DS-A
PMG3S-A
PMG3DS-A
PML3S-A
PML3DS-A
PMF4S-A
PMF4DS-A
PMP4S-A
PMP4DS-A
PMG4S-A
PMG4DS-A
PML4S-A
PML4DS-A
PMH4DSLM-A
Installation and Operation Manual
Surge Protective Devices (SPD)
1-800-800-4272 | www
.apc.com
Retain for future use
The APC SurgeArrest® Modular Panel Mount Products have
replaceable phase modules with integrated LED monitoring, a
display panel with surge counter and LED status indicators, an
audible alarm, and a NEMA 3R/12 Enclosure. Modular Panel
Products are available with 120kA and 160kA maximum surge
current per phase ratings.
PML-4Y-DC-DL-A
Page view 0
1 2 3 4 5 6 ... 19 20

Summary of Contents

Page 1 - Modular Panel Products

APC Modular Panel ProductsThe APC Modular Panel Product Surge Protective Devices (SPD) are designed to provide protection at the service entrance, bra

Page 2

SYSTEM GROUNDINGCAUTIONSYSTEM GROUNDING· SPD must be installed on solidly grounded power systems. · Verify that the service entrance equipment is b

Page 3 - IMPORTANT!

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH· Apply appropriate personal protective equipment (PPE) and follow safe electrical work pr

Page 4 - CONTENTS

Note: Prior to mounting the SPD, verify that the device has the same voltage rating as the power distribution system in which it is installed by compa

Page 5 - INTRODUCTION

WIRING DIAGRAMS WITHOUT INTEGRAL DISCONNECTFigure 3: Single-Phase, 3-Wire, GroundedChasis GroundChasis Ground ØC ØA NCustomer Connections 120 kA - 240

Page 6

8220-0014-06Customer Connections 320 kA - 480 kAØCØA NCustomer Connections 120 kA - 240 kA ØC ØA BØ NWIRING DIAGRAMS WITH INTEGRAL DISCONNECTChasis Gr

Page 7

The SPD display panel shows the status of the modules withOn wye and split phase configuration SPD modules (see Figure 7), if the left green LED is no

Page 8

Push the alarm enable/disable button to enable or disable the alarm. If the green alarm LED is lit the alarm is enabled. If the green alarm LED is not

Page 9 - NDERSIZED WIRING

The contacts are designed for a Maximum voltage of 24 VDC and a maximum current of 2 A. Higher energy applications may require additional relay implem

Page 10

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH· Apply appropriate personal protective equipment (PPE) and follow safe electrical work pr

Page 11

STARTPossible diagnosticdisplay board failure.Replace diagnosticdisplay panel. Is powerbeing suppliedto theSPD?Green phase LED(s)not lit. And, noRe

Page 12

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH· Apply appropriate personal protective equipment (PPE) and follow safe electrical work pract

Page 13 - Grounded Wye Installation

Entire contents copyright 2008 by American Power Conversion Corporation. All rights reserved. Reproduction in whole or in part without permission is p

Page 14 - Chasis Ground

CAUTIONLOSS OF SURGE PROTECTION· During installation into an electrical system, SPD’s must not be energized until the electrical system is compl

Page 15

CONTENTSINTRODUCTION ...UNPACKING AND PRELIMINARY INSPECTION ...

Page 16 - Note: Three phase model shown

INTRODUCTION Thank you for choosing the APC SurgeArrest® PM3 or PM4 Series Surge Protection Device. The APC modular Surge Protection Device (SPD) is

Page 17 - Terminals

Proper installation is imperative to maximize the APC Modular Panel SPD’seffectiveness and performance. The installer should follow the steps outline

Page 18

The identification nameplate (see Figure 1) is located on the inside of the door/cover.Figure 1: SPD Nameplate ExampleIDENTIFICATION NAMEPLATESAFETY L

Page 19

Prior to mounting the SPD, verify that the device has the same voltage rating as the power distribution system in which it is installed by comparing t

Page 20 - Entire contents copyright 2

The integral switch is a second mechanical means for qualified maintenance personnel to isolate the entire surge suppressor to service the device’s co