Back-UPS
BX650U-LM
Safety and General Information
Inspect the package contents upon receipt. Notify the
carrier and dealer if there is any damage.
Read the Safety Guide supplied with this unit before
installing the UPS.
User Guide
4
1
2
EN 990-5265 02/2014
© 2014 APC by Schneider Electric. APC, the APC logo and APC, the APC logo, Back-UPS, and PowerChute
are owned by Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are
property of their respective owners.
5
Status Indicators
This UPS is intended for indoor use only.
Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or
humidity.
Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
The battery typically lasts for three to five years. Environmental factors impact battery life. Elevated ambient
temperatures, poor quality AC power, and frequent short duration discharges will shorten battery life.
Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.
Battery Replacement
The battery in the Back-UPS BX650U-LM is not user-replaceable. Contact SEIT Technical Support for a list of
authorized service centers near you.
LED Audible Alarm Condition
On Off On-line - The Back-UPS is supplying utility power to the connected
equipment
Constant Tone On Line Overload - The power being used by the connected
equipment has exceeded the capacity of the unit. Disconnect some
equipment
Constant beeping Over-temperature Warning - The unit is overheating and will shut
down if the temperature is not lowered. Disconnect some of the
connected equipment.
On (Off
during 4
beeps)
4 beeps repeated
every 30 seconds
On-Battery - The Back-UPS is supplying battery power
Flashing Rapid Beeping
(every 1/2 second)
Low Battery Warning - The Back-UPS has 2 minutes of runtime
remaining
Constant tone Bad Battery Detected - The battery needs to be charged, or is at end
of life. (See Battery Replacement.)
Chirp every 2
seconds
Charger Warning - The Back-UPS has experienced an internal
problem, but is still providing power to the connected equipment.
Contact Schneider Electric IT (SEIT) Technical Support
Off Short beep every
4 seconds
Low Battery Shutdown - During On Battery operation the battery
power was almost completely exhausted, and the Back-UPS is waiting
for utility power to return to normal
Constant Tone On Battery Overload - The connected equipment requires more
power than provided by the Back-UPS battery. Unplug devices one at a
time to remove overload. If the problem is not corrected, contact SEIT
Technical Support
Constant Tone Charger Fault - Back-UPS has an internal problem, and is no longer
powering the load. Contact SEIT Technical Support
Constant Tone Temperature Fault - The Back-UPS has overheated and has shut
down.
Connect the Battery
PowerChute
Personal Edition Software
PowerChute Personal Edition Software allows you to use your computer to access additional power protection
and management features of the Back-UPS.
Installation
Connect the Back-UPS to a computer using a USB cable. Plug one end into the USB Port on the rear panel of the
Back-UPS and the other into a USB port on your computer.
To download the software and for detailed operation, go to www.apc.com
bu384a
3
Connect the battery by pulling the battery connector
handle down, and then pushing it into the unit.
Connect the Back-UPS BX650U-LM power cable
directly to a wall outlet. Do not use surge protectors or
extension cords.
Press the ON/OFF button to turn on the unit.
The green “Power On” indicator confirms that the Back-UPS is on and ready to provide
protection.
The Back-UPS should charge for at least 10 hours to ensure sufficient runtime. The unit is
being charged whenever it is connected to AC power, whether the unit is turned ON or OFF.
2
1
3
Installation
Transfer Voltage and Sensitivity
Settings
Automatic Voltage Regulation boosts the AC voltage when it drops below safe levels. This allows the
equipment that is connected to the Back-UPS to operate during low voltage conditions. Automatic Voltage
Regulation will also regulate high voltage conditions down to a safe level.
The Back-UPS will switch to battery power if the AC input voltage level becomes too low or too high for the
Automatic Voltage Regulation feature to compensate, or if the AC power is experiencing voltage fluctuations.
No-load Shutdown
The UPS will shut down to conserve energy if while operating on battery power the UPS detects that connected
equipment is using less than 15 W of energy for more than 15 minutes.
No-load shutdown can be enabled or disabled through Program mode described below.
If the Back-UPS switches to battery power too frequently or too infrequently, adjust the transfer voltage and
sensitivity settings:
1 . Verify that the Back-UPS battery is connected. Connect the Back-UPS to a wall outlet.
The Back-UPS should be turned off.
2 . Press and hold the POWER ON/OFF button until the LED flashes rapidly. Release the button. The Back-
UPS is now in Program mode.
3 . Immediately press the POWER ON/OFF button to change the current setting. Press and release the
POWER ON/OFF button to scroll through available settings. The LED will flash once, twice or three
times and emit audible beeps to indicate the voltage sensitivity level. Refer to the table for an
explanation of the transfer voltage sensitivity levels.
4 . To exit Program mode wait five seconds and the LED will extinguish. Program mode is no longer
active.
APC by Schneider Electric IT Customer
Support Worldwide
For country specific customer support, go to the APC by Schneider Electric Web site, www.apc.com.
Register your product on-line. http://warranty.apc.com
LED
Flashing
Audible
Indicator
Transfer
Voltage
Setting
Input
Voltage
Range
No-load
Shutdown Description
Once per
second
None Low 78-150 Disabled The Back-UPS will switch to battery power less
often. Use this setting for equipment that is not
sensitive to low or high level voltage levels or
minor voltage waveform distortions.
Once per
second
4 beeps
per second
Low 78-150 Enabled The Back-UPS will switch to battery power less
often. Use this setting for equipment that is not
sensitive to low or high level voltage levels or
minor voltage waveform distortions.
Twice
per
second
None Medium 81-147 Disabled Use when the input utility power is normal,
without any fluctuation in voltage levels.
Twice
per
second
4 beeps
per second
Medium
(factory
default)
81-147 Enabled Use when the input utility power is normal,
without any fluctuation in voltage levels.
Three
times
per
second
None High 81-144 Disabled The Back-UPS will switch to battery power
during any small fluctuation in voltage. Use this
setting for equipment that is sensitive to low or
high level voltage levels or minor voltage
waveform distortions.
Three
times
per
second
4 beeps
per second
High 81-144 Enabled The Back-UPS will switch to battery power
during any small fluctuation in voltage. Use this
setting for equipment that is sensitive to low or
high level voltage levels or minor voltage
waveform distortions.
6
7
Troubleshooting and Service
1 . Consult the Troubleshooting from the APC by Schneider Electric Web site, www.apc.com.
2 . If the problem persists, contact Schneider Electric IT (SEIT) Customer Support through the Schneider
Electric Web site, www.apc.com.
a. Note the model number and serial number and the date of purchase. The model and serial numbers are
located on the rear panel of the unit and are available through the LCD display on select models.
b. Call SEIT Customer Support and a technician will attempt to solve the problem over the phone. If this
is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free.
d. Service procedures and returns may vary internationally. Refer to the Schneider Electric Web site for
country specific instructions.
3 . Prepare to troubleshoot the problem over the phone. If this is not successful, and the unit is still under
warranty, the Technical Support Representative will provide all necessary information to return the unit for
replacement
Input
Voltage 120 Vac, nominal
Frequency 50/60 Hz ± 3Hz, auto-sensing
Brownout Transfer 78 Vac, typical
Over-voltage Transfer 150 Vac, typical
Output
UPS Capacity (total) 650 VA / 390 W
Voltage On Battery 120 Vac (step-approximated sinewave)
Frequency on Battery 50/60 Hz ± 1Hz
Transfer Time 4 ms typical
Protection and
Filtering
AC Surge Protection Full time, 343 Joules
AC Input Resettable circuit breaker
Battery
Type (maintenance free, lead acid) 12 V 7.2 Ahr
Average Life 3 - 5 years depending on the number of discharge
cycles and environmental temperature
Typical Recharge Time 8 Hours
Physical
Net Weight 6.2 kg
Dimensions (H x W x D) 20 cm x 11.5 cm x 25.7 cm
Operating Temperature 0
o
C to 40
o
C (32
o
F to 104
o
F)
Storage Temperature -15
o
C to 45
o
C (5
o
F to 113
o
F)
Operating Relative Humidity 0 to 95% non-condensing
Operating Elevation 0 to 3000 m (0 to 10,000 ft)
EMC
Compliance
This device complies with part 15 of the FCC rules. Operation is subject to the
following two conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including interference that may
cause undesired operation.
Inventory
e
On/Off button
Battery connector
Circuit breaker
USB port
Telephone/Network port
AC Power Cable
Battery Backup + Surge
Protection outlets
Specifications