APC G7TUPS250 Installation Manual

Browse online or download Installation Manual for Uninterruptible power supplies (UPSs) APC G7TUPS250. APC G7TUPS250 uninterruptible power supply (UPS) User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 68
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
MGE
Galaxy
7000
160 - 500 kVA
Installation manual
Single UPS
Modular UPS
Parallel UPS with SSC
Frequency converters
Static-switch cabinet
Page view 0
1 2 3 4 5 6 ... 67 68

Summary of Contents

Page 1 - 160 - 500 kVA

MGE™ Galaxy™ 7000160 - 500 kVAInstallation manualSingle UPSModular UPSParallel UPS with SSCFrequency convertersStatic-switch cabinet

Page 2 - Introduction

Possible installations > Parallel UPS systems34020846EN/AE - Page 101. InstallationParallel UPSs with SSC (static-switch cabinet) Parallel UPSs wi

Page 3 - Foreword

Possible installations >34020846EN/AE - Page 111. InstallationUPS set up as a frequency converter (with or without battery, maximum eight units)Sin

Page 4 - Safety rules

Layout >34020846EN/AE - Page 121. Installation1.2 LayoutDimensionsWeightsWeight values are purely indicative. See the packing labels for the precis

Page 5 - Environment

Layout >34020846EN/AE - Page 131. InstallationFloor mounting Normal or false floor.UPS cabinets SSC800 and 1200 kVA2000 kVADimensions are indicated

Page 6 - Contents

Layout > Floor mounting34020846EN/AE - Page 141. Installation2000 kVA light External bypass or SSC maintenance cabinets 800 and 1200 kVA2000 kVA

Page 7

Layout > Floor mounting34020846EN/AE - Page 151. InstallationAuxiliary cabinets (empty) Backfeed cabinet Max. load on floor per square cm for

Page 8

Layout >34020846EN/AE - Page 161. InstallationPosition in room UPS cabinetsSSCsLayout example for an SSC with two parallel UPS units External bypas

Page 9

Layout >34020846EN/AE - Page 171. InstallationVentilation UPS cabinetsSSCsPn = rated power; for other values, please consult the after-sales suppor

Page 10 - 1. Installation

Prerequisites >34020846EN/AE - Page 181. Installation1.3 PrerequisitesUPS currentsRecommended upstream protection Normal AC source Bypass AC sour

Page 11

Prerequisites >34020846EN/AE - Page 191. InstallationRecommended maximum downstream protection Battery protection Pn = rated power at a power fact

Page 12

34020846EN/AE - Page 2Introduction Thank you for selecting an APC by Schneider Electric product to protect your electrical equipment.The MGE™ Gal

Page 13

Prerequisites >34020846EN/AE - Page 201. InstallationCharacteristics of the connection terminals UPS cabinets* Maximum tightening torque: 25 N.mSSC

Page 14

Prerequisites >34020846EN/AE - Page 211. InstallationPower cables for parallel UPSs Normal AC line and batteryBypass AC line and loadModular UPSs i

Page 15

Prerequisites > Power cables for parallel UPSs34020846EN/AE - Page 221. InstallationFrequency converters 1 Do not include redundant UPS units.Modu

Page 16

Prerequisites > Power cables for parallel UPSs34020846EN/AE - Page 231. InstallationParallel UPSs with SSC (static-switch cabinet) 1 Do not includ

Page 17

System earthing arrangements >34020846EN/AE - Page 241. Installation1.4 System earthing arrangementsThis section lists the main SEAs (system earthi

Page 18

System earthing arrangements > Parallel UPS systems34020846EN/AE - Page 251. InstallationTNC upstream, TNC, TNS or TT downstream installation For

Page 19

Adapting the cabinet according to the neutral point connection >34020846EN/AE - Page 261. Installation1.5 Adapting the cabinet according to the neu

Page 20

Connecting the power cables >34020846EN/AE - Page 271. Installation1.6 Connecting the power cablesSingle or modular UPS cabinet 160 to 400 kVARemov

Page 21

Connecting the power cables > Single or modular UPS cabinet34020846EN/AE - Page 281. Installation500 kVARemove the protective coversThis operation

Page 22

Connecting the power cables >34020846EN/AE - Page 291. InstallationFrequency-converter cabinet160 to 400 kVARemove the protective coversIn parallel

Page 23

34020846EN/AE - Page 3ForewordPictograms Document Danger, these instructions are imperative Audio signalInformation, advice, help. LED offVisual

Page 24

Connecting the power cables > Frequency-converter cabinet34020846EN/AE - Page 301. Installation500 kVARemove the protective coversIn parallel syst

Page 25

Connecting the power cables >34020846EN/AE - Page 311. InstallationParallel UPS cabinet250 to 400 kVARemove the protective coversIn parallel system

Page 26

Connecting the power cables > Parallel UPS cabinet34020846EN/AE - Page 321. Installation500 kVARemove the protective coversIn parallel systems wit

Page 27

Connecting the power cables >34020846EN/AE - Page 331. InstallationStatic-switch cabinet800 kVARemove the protective coversThis operation must be c

Page 28

Connecting the power cables > Static-switch cabinet34020846EN/AE - Page 341. Installation1200 kVARemove the protective coversThis operation must b

Page 29

Connecting the power cables > Static-switch cabinet34020846EN/AE - Page 351. Installation2000 kVARemove the protective coversYou must have first a

Page 30

Connecting the power cables > Static-switch cabinet > 2000 kVA34020846EN/AE - Page 361. InstallationConnecting the power cablesThis operation m

Page 31

Connecting the power cables > Static-switch cabinet34020846EN/AE - Page 371. Installation2000 kVA lightRemove the protective coversThis operation

Page 32

Connecting the power cables > Static-switch cabinet > 2000 kVA light34020846EN/AE - Page 381. InstallationConnecting the power cablesThis opera

Page 33

Connecting the power cables >34020846EN/AE - Page 391. InstallationExternal bypass cabinet800 kVARemove the protective coversThis operation must be

Page 34

34020846EN/AE - Page 4SafetySafety rulesSafety of persons Product safety◗ Protection (circuit breaker/switch disconnector) must be installed upstream

Page 35

Connecting the power cables > External bypass cabinet34020846EN/AE - Page 401. Installation1200 kVARemove the protective coversThis operation must

Page 36

Connecting the power cables > External bypass cabinet34020846EN/AE - Page 411. Installation2000 kVARemove the protective coversThis operation must

Page 37

Connecting the power cables >34020846EN/AE - Page 421. InstallationSSC maintenance cabinet800 and 1200 kVARemove the protective coversThis operatio

Page 38

Connecting the power cables > SSC maintenance cabinet34020846EN/AE - Page 431. Installation2000 kVARemove the protective coversThis operation must

Page 39

Connecting cabinet ECPs (exposed conductive parts) >34020846EN/AE - Page 441. Installation1.7 Connecting cabinet ECPs (exposed conductive parts)Val

Page 40

Connect the backfeed option >34020846EN/AE - Page 451. Installation1.9 Connect the backfeed optionThe backfeed option on normal and bypass AC input

Page 41

Connecting the control-wire cables >34020846EN/AE - Page 461. Installation1.10 Connecting the control-wire cablesConnecting a modular UPS or freque

Page 42

Connecting the control-wire cables >34020846EN/AE - Page 471. InstallationConnecting the UPS units in parallelConnecting the modular UPS units in p

Page 43

Connecting the control-wire cables > Connecting the UPS units in parallel34020846EN/AE - Page 481. InstallationConnecting the modular UPSs with th

Page 44

Connecting the control-wire cables > Connecting the UPS units in parallel34020846EN/AE - Page 491. InstallationConnecting parallel UPSs with SSC (

Page 45

34020846EN/AE - Page 5EnvironmentAPC by Schneider Electric has implemented an environmental protection policy.Products are developed according to an e

Page 46

Connecting the control-wire cables > Connecting the UPS units in parallel34020846EN/AE - Page 501. InstallationConnect the components specific to

Page 47

Connecting the control-wire cables > Connecting the UPS units in parallel > Connect the components specific to the 2000 kVA light SSC34020846EN

Page 48

Connecting the control-wire cables > Connecting the UPS units in parallel34020846EN/AE - Page 521. InstallationConnect the SSC maintenance cabinet

Page 49

Connecting the control-wire cables >34020846EN/AE - Page 531. InstallationConnecting the EPO function This operation must be carried out by qualifi

Page 50

Connecting the control-wire cables >34020846EN/AE - Page 541. InstallationConnecting the dry-contact communication card This operation must be carr

Page 51

Coupling the 400 mm auxiliary cabinet >34020846EN/AE - Page 551. Installation1.11 Coupling the 400 mm auxiliary cabinet1 - Remove the two inter-cab

Page 52

Assembling and connecting the external battery cabinet >34020846EN/AE - Page 561. Installation1.12 Assembling and connecting the external battery c

Page 53

Assembling and connecting the external battery cabinet >34020846EN/AE - Page 571. InstallationConnecting the power cables4 - Connect the control-wi

Page 54

Assembling and connecting the external battery cabinet >34020846EN/AE - Page 581. InstallationConnecting the control-wire cablesConnecting the batt

Page 55

Assembling and connecting the external battery cabinet >34020846EN/AE - Page 591. InstallationConnecting the battery temperature sensor UPS cabinet

Page 56

34020846EN/AE - Page 6Contents1. Installation 1.1 Possible installations...

Page 57

34020846EN/AE - Page 60Connecting a sensor to a number of UPS cabinets1 - Connect the UPSs to the temperature sensor in the auxiliary cabinet as per t

Page 58

Assembling 2000 kVA SSCs >34020846EN/AE - Page 612. Appendices2. Appendices2.1 Assembling 2000 kVA SSCs2.2 IP 32 optionRefer to the "IP 32&quo

Page 59

Electrical characteristics >34020846EN/AE - Page 622. Appendices2.3 Electrical characteristicsSelection of protection devices UPS short-circuit cur

Page 60 - XM 21 XM 21 XM 21

Electrical characteristics >34020846EN/AE - Page 632. AppendicesPermissible UPS overloads as a function of time NORMAL mode operation Bypass AC m

Page 61 - 2. Appendices

General characteristics of MGE™ Galaxy™ 7000 UPSs >34020846EN/AE - Page 642. Appendices2.4 General characteristics of MGE™ Galaxy™ 7000 UPSsUPS pow

Page 62

General characteristics of MGE™ Galaxy™ 7000 UPSs >34020846EN/AE - Page 652. AppendicesBattery characteristics Sealed lead-acid battery Vented lea

Page 63

Glossary >34020846EN/AE - Page 662. Appendices2.5 Glossary Backup time Time that the connected loads can operate on battery power.Bypass AC source

Page 64

Glossary >34020846EN/AE - Page 672. Appendices

Page 65

34020846EN/AE

Page 66

34020846EN/AE - Page 7Contents1.5 Adapting the cabinet according to the neutral point connection ... 2

Page 67

34020846EN/AE - Page 8Contents1.12 Assembling and connecting the external battery cabinet.....

Page 68 - 34020846EN/AE

34020846EN/AE - Page 91. Installation1.1 Possible installationsSingle or modular UPS alone Parallel UPS systems (8 units maximum)Modular UPSs in paral