APC GALAXY 990-2258B-001 User Manual

Browse online or download User Manual for Uninterruptible power supplies (UPSs) APC GALAXY 990-2258B-001. APC GALAXY 990-2258B-001 User's Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 6
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
990-2258B-001
9/2009
*990-2258B-
Installation
MGE™ Galaxy™ 3500
10-40 kVA 380/400/415 V with batteries
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
Warning: ALL safety instructions in the Safety Sheet
(990-2940) must be read, understood, and followed when
installing the UPS system. Failure to do so could result in
equipment damage, serious injury, or death.
Warning: After the UPS has been electrically wired, do
not start it up. Start-up is commissioned to authorized
personnel from Schneider Electric.
Caution: All electrical power and power control wiring
must be installed by a qualified electrician, and must comply
with local and national regulations for maximum power
rating.
Note: Ensure that the unit is in its final location prior to
installation.
Note: Battery and utility/mains power must not be
connected until all other wiring has been completed.
See Also: For parallel configurations see manual 990-
3568.
Level the Enclosure
Warning: The system must be installed on a level floor.
The leveling feet will stabilize the enclosure, but will not
account for a badly sloped floor.
Use a 13/14 mm wrench to adjust the four leveling feet.
Ensure that the system is level.
Caution: Do not move the enclosure after the leveling feet
have been lowered.
Floor Anchoring (if applicable)
Anchor the UPS enclosure to the floor
Note: Floor-anchoring bolts are not provided with the UPS.
Purchase the bolts locally (minimum size: M8). Follow the
specifications given by the manufacturer of the floor
anchoring system when bolting the UPS system to the floor.
Reuse the two transport brackets (one
on each side) that were used to secure the
UPS to the pallet during transport.
Drill two to six holes in the floor for
each bracket. Attach with bolts.
Prepare for Cables
Bottom cable entry
From the rear of the UPS, loosen the six
M4 screws from the upper cover (the cable
landing area) on the back and remove.
Route the cables from the
slanted back plate, up
through the punched
bracket, and into the cable
landing area.
Fasten the cables with
cable ties
Note: A conduit box (part no. SUVTOPT001 or
SUVTOPT002) is available as an option.
UPS
UPS
XR battery enclosure
Page view 0
1 2 3 4 5 6

Summary of Contents

Page 1 - Installation

990-2258B-0019/2009*990-2258B-InstallationMGE™ Galaxy™ 350010-40 kVA 380/400/415 V with batteriesIMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONSW

Page 2 - Dual mains

2Connect the AC Input and AC Output CablesWarning: Use compression type lugs ONLY. Do not loosen or add cables to any factory preinstalled cables on b

Page 3

3EPO wiring – pin connections J108. Connect the EPO cable using one of the following four wiring configurations.Pin connections J106 (UPS). Note: Wh

Page 4 - Specifications

4 Remove the two screws from the cable-inlet at the front and remove the cable-inlet plate. Guide the cable through the hole in the bottom plate and

Page 5 - Minimum breaker settings

5Bypass inputNotes1 Input current based on rated load and batteries fully charged.2 Input current based on full battery recharge, nominal voltage and

Page 6 - Appendix

6Contact InformationFor local, country-specific centers: go to www.apc.com/support/contact.AppendixWiring diagramsDiagram with Maintenance Bypass Pane

Comments to this Manuals

No comments