CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
1
APC InfraStruXure for Small Data Centers, 20kW Base Building Block
GUIDE SPECIFICATIONS FOR
10kW-20kW UPS/Distribution
PART 1 - GENERAL
1.1 SUMMARY
A. This specification describes the operation and functionality of a continuous duty, three-
phase, solid-state, static Uninterruptible Power System (UPS) hereafter referred to as
the UPS. The UPS shall utilize an N+1 redundant, scalable array architecture. The
system power train shall be comprised of hot swappable / user replaceable
10kW/10kVA power modules, which shall operate in parallel, and be configured for
N+1 redundant operation at rated load. Each 10kVA/10kW power module contains a
full rated input rectifier / boost converter (hereafter referred to as Input Converter), full
rated output inverter, and 10% battery charging circuit. The system shall also comprise
of a user-replaceable continuous duty bypass static switch module, hot swappable / user
replaceable battery modules, redundant control modules, redundant logic power
supplies, and LCD interface display. System static switch shall be capable of being fed
from the same input as the rectifier or a separate input. All of the above system
components are housed in two standard, 24 inch wide, 36 inch deep, 42U high
equipment racks.
B. In addition, this specification describes the performance, functionality, and design of
the UPS Maintenance Bypass Cabinet and power distribution section of the UPS. In
addition this specification also includes multi-conductor overhead distribution, rack
level power management products, the Battery System, and connectivity solutions
including complete InfraStruXure
TM
system management solutions.
C. The UPS and associated equipment shall operate in conjunction with a primary power
supply and an output distribution section to provide quality uninterrupted power and
distribution for mission critical, electronic equipment load. The entire system shall bear
the UL60950 listing as a complete product solution.
D. All programming and miscellaneous components for a fully operational system as
described in this specification shall be available as part of the System.
1.2 STANDARDS
A. UL 1778 Uninterruptible Power Supply Equipment
B. UL60950 Information Technology Equipment
Page view 0
1 2 3 4 5 6 ... 17 18

Summary of Contents

Page 1 - 10kW-20kW UPS/Distribution

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 1APC InfraStruXure for Small Data Cen

Page 2

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 1039. UPS in Bypass due to Internal

Page 3

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 11 a. Normal Operation b. Battery Op

Page 4

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 123.3 OUTPUT DISTRIBUTION PANEL A.

Page 5

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 132. Outlet Management - The outlets

Page 6

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 141. The Enclosure shall be designed

Page 7

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 15Seismic rated floor stands shall be

Page 8

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 16j. SCO UNIX k. SVR4 2.3, 2.41 m. SC

Page 9

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 174. Inspect Battery Units. 5.

Page 10

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 18 9. Document, sign, and date all

Page 11 - 2.8 BATTERY

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 2C. Where applicable, the UPS shall

Page 12

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 32. Product catalog sheets or equipm

Page 13

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 4 3. Short Circuit Withstand Rating:

Page 14

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 52) 1000% for 500 milliseconds 9.

Page 15

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 6 2. In cases where the source volta

Page 16

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 72.6 STATIC BYPASS A. As part of the

Page 17

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 8B. Display Unit: A microprocessor c

Page 18

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 913. Number of Power Modules decreas

Comments to this Manuals

No comments