Page 1 - 250 - 600 kVA

6739380EN/JC - Page 1User manualSingle-unit UPSModular UPSParallel UPS with SSCFrequency converterStatic Switch CubicleMGETM GalaxyTM 600050, 60 Hz250

Page 2 - Page 2 - 6739380EN/JC

Page 10 - 6739380EN/JCI+–!!O2beep...beep...This signal warns the user of theimminent end of battery power. On thedevice itself, the buzzer beepsincrea

Page 3 - Contents

6739380EN/JC - Page 11I+–!!O2beep...beep...1Example of an installation with an engine generator setInstallation with an enginegenerator set(figure 15)

Page 4 - Contents (cont.)

Page 12 - 6739380EN/JCFrequency converters withredundancy◗ the shutdown of one unit is of noconsequence for the load. The otherlines each take up an e

Page 5 - Introduction

6739380EN/JC - Page 13374'4113125108911222 2226Inverter cubicle250 to 400kVA UPS or frequency converterfront view, doors open, protective covers

Page 6

Page 14 - 6739380EN/JC800 kVA UPSFig. 21front view, doors open, protective covers removedBattery cubicle(for a 250 to 300kVA UPS)front view, doors ope

Page 7

6739380EN/JC - Page 15Static Switch Cubiclefront view, doors open, protective covers removedFig. 23Static Switch Cubicles are rated 500,800, 1200 and

Page 8

Page 16 - 6739380EN/JC5!!3215I+–!!O4321 6 7MGETM GalaxyTM 6000 control panels(see figure 25) are made up of:◗ a visible panel with the basic controlsa

Page 9

6739380EN/JC - Page 17I+–!!Obeep...beep...1I+–!!O2I+–!!O3I+–!!O4I+–!!O5I+–!!O6Buzzer 1The buzzer sounds in the followingsituations:◗ load supplied by

Page 10 - Introduction (cont.)

Page 18 - 6739380EN/JC7I+–!!OThe hidden panel, located behind thehinged cover, offers the followingindications and control functions:◗ environment fau

Page 11

6739380EN/JC - Page 19Light A - emergency shutdownThis red light signals that the remote"emergency shutdown" button waspressed (external inf

Page 12

Page 2 - 6739380EN/JC

Page 13 - 6000 cubicles

Page 20 - 6739380EN/JCI+–!!O6I+–!!O2I+–!!O6Start-up◗ close inverter output switch Q5N:◗ close battery circuit breaker QF1:◗ open maintenance bypass sw

Page 14 - 6000 cubicles (cont.)

6739380EN/JC - Page 21I+–!!O6I+–!!O2Modular UPS with externalmaintenance bypassProceed in the following order:◗ check that all lines supplying the loa

Page 15

Page 22 - 6739380EN/JCI+–!!O6Q1 Q5NOFFON(0)(I)ON(I)Start-up (cont.)◗ close fuse switch Q1 in the StaticSwitch Cubicle;◗ close input switch Q1 on an UP

Page 16 - Control panel

6739380EN/JC - Page 23Frequency converter or multi-bypassUPS:◗ the inverter starts and awaits thestart of the other inverters;◗ when they are all on o

Page 17 - Control panel (cont.)

Page 24 - 6739380EN/JCI+–!!O7ShutdownShutdown of a unitModular UPS with externalmaintenance bypass:◗ all the UPSs shut down:◗◗ green "load protec

Page 18

6739380EN/JC - Page 25System shutdown◗◗ open Mains 2 input switch Q4S:◗◗ open battery circuit breaker QF1:◗◗ open Mains 1 input switch Q1:◗ the UPS is

Page 19

Page 26 - 6739380EN/JCABCDEFGH I JKLMN12 34511Frequency converters(no Mains 2)Shutdown of the inverters results in theinterruption of the load;◗ shut

Page 20 - Start-up

6739380EN/JC - Page 27I+–!!O7AlarmsThe autodiagnostic system considersany system status other than normal asa problem.Prior to any other action, note

Page 21 - Start-up (cont.)

Page 28 - 6739380EN/JCEnvironment informationStandard information Media Contacts 9Remote transmission board◗ battery circuit breaker QF1 closed:a NO c

Page 22

6739380EN/JC - Page 29"LED" signalling box (optional)Additional information "Media Contacts 15" (optional)Additional remote transm

Page 23

6739380EN/JC - Page 3ContentsIntroductionSystem performance ...

Page 24 - Shutdown

Page 30 - 6739380EN/JCSignal transmissionThese signals are each transmitted bytwo volt-free changeover contacts witha maximum breaking capacity of 5A2

Page 25 - Shutdown (cont.)

6739380EN/JC - Page 31MaintenanceMaintenance configurationFig. 29Caution:◗ work should be carried out inaccordance with applicable safetyregulations;◗

Page 26

Page 32 - 6739380EN/JCMaintenance (cont.)Frequency converter or parallelUPS with SSC(figure 32)During maintenance, the concernedUPS or converter must

Page 27 - Maintenance bypass

6739380EN/JC - Page 33Static Switch CubicleDuring maintenance, the Static SwitchCubicle must be isolated from Mains 2,the load and the parallel UPSs.◗

Page 28 - Environment information

Page 34 - 6739380EN/JCVisual check◗ clean the system regularly,particularly the air inlet and outlet grills.Check that the air circulates freely inthe

Page 29 - (cont.)

6739380EN/JC - Page 35Training centersTraining centersSchneider Critical Power & cooling services50 Hz :France Training Centre140, Avenue Jean Kun

Page 30

Page 36 - 6739380EN/JC"Monitor" alphanumeric displayGeneralFig. 34Alphanumeric display screen and control panelThe alphanumeric display scre

Page 31 - Maintenance

6739380EN/JC - Page 37"Monitor" alphanumeric display (cont.)">" button 20This button has a number of functionsdepending on the

Page 32 - Maintenance (cont.)

Page 38 - 6739380EN/JCAlarm display and buzzer resetDisplay of alarmsThis message is displayed only if the buzzer hasbeen activated. It is a prompt to

Page 33

6739380EN/JC - Page 39List of secondary alarmsThese alarm messages may beconsulted by pressing the "alarms" ("!")button when the &

Page 34

Page 4 - 6739380EN/JCContents (cont.)All MGETM GalaxyTM 6000 products are protected by patents. They implement original APC by Schneider Electric tech

Page 35 - Training centers

Page 40 - 6739380EN/JCFREQUENCY REVERSALAUXILIARY CONTROLThe UPS has received a command tochange its output frequency (50 or60Hz).This command is only

Page 36

6739380EN/JC - Page 41UPS IMPOSEDTRANSFER DISABLE !Cannot transfer the load to Main 2 dueto:◗ transfer conditions not satisfied;◗ UPS operating on an

Page 37 - 6739380EN/JC - Page 37

Page 42 - 6739380EN/JCVoltage measurementsDisplay of voltage measurementsDirect access to the functionby pressing the "V" button.Mains 1 inp

Page 38

6739380EN/JC - Page 43Frequency and power measurementsDisplay of power and frequency measurementsDirect access to the function by pressing the"W.

Page 39

Page 44 - 6739380EN/JCDisplay of battery measurements (cont.)◗ battery test: see figure opposite.✴✴The screen opposite is displayed when abattery test

Page 40

6739380EN/JC - Page 45Inverter On/Off commandsDisplay for the inverter On/Off commandsDirect access to the function by pressingthe "I/O" but

Page 41 - Measurement system

Page 46 - 6739380EN/JCDisplay system configurationDisplay system configurationThis function may be accessed from the initialscreen. Press the "*&

Page 42 - Current measurements

6739380EN/JC - Page 47"LED" signalling boxOptionsThis unit remotes the basic elements ofinformation on system status:◗ load on battery;◗ low

Page 43 - Battery measurements

Page 48 - 6739380EN/JCInsulating and Mains 1, Mains 2 and load voltage matching transformerHarmonics filter and power factor improvementThis option, p

Page 44

6739380EN/JC - Page 49Empty cubiclesCubicles may be supplied empty, thusenabling users to make up their ownauxiliary cubicles (battery cubicles orothe

Page 45 - Inverter On/Off commands

6739380EN/JC - Page 5IntroductionSystem performanceSystem descriptionNote:◗ the Mains 1 normal input and theMains 2 bypass input have differentfuncti

Page 46 - Display system configuration

Page 50 - 6739380EN/JC6739380EN-JC

Page 47 - XR5 XR6 XR7XR9XR8

Page 6 - 6739380EN/JCIntroduction (cont.)Different types of MGETMGalaxyTM 6000 systemsFig. 1◗ Single-unit or modular UPS:(figure 1)◗ Multi-bypass modu

Page 48 - "Vision" display

6739380EN/JC - Page 7Fig. 6Fig. 5Fig. 4◗ Frequency converter with batterybackup power: (figure 4)◗ Frequency converter without backuppower: (figure 5)

Page 49 - Options (cont.)

Page 8 - 6739380EN/JCIsolation and protection devicesExample of a single-unit UPS or single modular UPSFig. 8Fig. 9Static Switch Cubicle(figure 9)◗ Q4

Page 50 - 6739380EN-JC

6739380EN/JC - Page 95I+–!!O4beep...beep...légend :off on5I+–!!OMain operating modes(1) Except for frequency converters without abatteryFig. 11The vol