MGEGalaxy500040-130kVA480VOperation
UPSCongurationAccesstothePersonalizationFunctionsCaution:PersonalizationmustbecarriedoutwithswitchesQ1(8)andQ5N(11)open(OFF)andswitchQ4S(9)closed(ON)
AutomaticBypassFunctionFactorysettingOptionsTransfertobypassACsourceEnabledDisabled–disabledwhenlimitingTransfertobypasswithbypassACsourceoutoftoleran
OperationCaution:Alloperationsconcerningsystemstart-upandcompliancewithstandardsandregulations,includingthoserelatedtothebatterycabinet,mustbecarriedo
3.BothnormalandBypassACsourcesnotavailableoroutoftolerance:LED(B)isON.Thebuzzersoundsintermittently.TheloadissuppliedbytheUPSfrombatterypower.Note:The
OperationofMimic-PanelLEDsTheMGEGalaxy5000systemissimpletooperateandyetprovidesawealthofcontinuousmonitoringanddiagnosticfeaturestoensureproperoperati
OperationProceduresShutDownaSingleUPSTheUPSremainsenergizedunlessitisshutdown.1.Pressabuttontoexitsleepmode.2.PresstheOFFbutton(A)for3seconds.Theloadi
RestartaSingleUPSCheckthatswitchesQ4S(B)andQ5N(C)areclosed.Ifthisisthecase,continuewiththisprocedure,otherwisereferto“ReturntotheNormalOperation,Singl
ShutDownaParallelConguration1.Pressabuttononeachunittoexitsleepmode.2.PresstheOFFbutton(A)oneachunitfor3seconds.TheloadisnolongerprotectedbytheUPSs.I
RestartaParallelCongurationCheckthatswitchesQ4S(B)andQ5N(C)areclosed.Ifthisisthecase,continuewiththisprocedure,otherwisereferto“ReturntoNormalOperati
IsolateUPSIsolateSingleUPSToisolatetheUPSfromtheelectricalpowersourceandsupplytheloaddirectlybythenormalorbypassACsource,followtheinstructionsbelow:1.
IsolateParallelUPSWithoutExternalBypassCabinetShutdownandisolatetherstUPS:1.CheckthatthetwoUPSsareoperating.2.Pressabuttontoexitsleepmode.3.Shutdownt
IsolateParallelUPSWithExternalBypassCabinetShutdownandisolateoneUPS:1.CheckthatthetotalcapacityoftheremainingUPSsissufcienttosupplytheconnectedload.2
ReturntoNormalOperationReturntoNormalOperation,SingleUPS1.CheckthatbypassswitchQ3BP(C)isONandthatallotherswitchesareOFF.2.SetswitchQ4S(B)toON.3.Setout
ReturntoNormalOperation,ParallelUPSWithoutExternalBypassCabinetRestarttheUPSUnitforwhichSwitchQ3BP(10)isONandtheOtherSwitchesareOFFCaution:Itisimperat
RestarttheUPSforwhichAllSwitchesareSettoOFF1.SettheinputswitchQ4S(B)toON.2.SetoutputswitchQ5N(D)toON.3.CheckthatalltheUPSunitspresentintheinstallation
ReturntoNormalOperation,ParallelUPSWithExternalBypassCabinet1.CheckthatallswitchesontheUPSsaresettoOFF.2.ApplybypassandinputpowertoUPSs.3.SetswitchQ4S
OperationoftheRelayCommunicationCard(DryContacts)Allsystemsareequippedwiththisremotetransmissionscard(alsoknownasSECI).Acompletespecicationexistsfort
ProgrammableModeThisoperatingmodeisspecictotheMGEGalaxy5000.Microswitch3onSA1mustbesettoON(iftwoSECIcardsareinstalledintheunit,thesecondcardmustbeide
OperatingstatusconditionsDescriptionPFCFAULTNeutrallegfaultORNeutrallegIGBTtemperatureoutsidetolerancesOR-V oltagedifferencebetween2DChalf-busesoutsid
OperatingstatusconditionsDescriptionBATTERYCIRCUITBREAKER(S)OPENOneortwoBatterycircuitbreakersisopen.PHASEROTA TIONFAULTPhaseinversiononnormalACinputO
TableofContentsAboutThisManual...1SymbolsUsed...
MaintenanceLifeCycleMonitoring(LCM)The“LifeCycleMonitoring”(LCM)functionprovidesUPSmaintenanceadvicetoguaranteeinstallationavailabilityfortheuser.Thed
ServicingBatteriesIMPORTANTSAFETYINSTRUCTIONSFORSERVICINGBATTERIESServicingofbatteriesshouldbeperformedorsupervisedbypersonnelknowledgeableofbatteries
TroubleshootingIdenticationofAlarmsAlarmconditionsareidentiedbyLEDs(A),(B),(C)andthebuzzer.LED(A)LED(B)LED(C)BuzzerSignicance--IntermittentNormalAC
AlarmorStatusDisplayMessagesListDisplayMessageLevelAbnormalbypassoperationInternalandexternalswitchesAbnormalexternalbypassoperationInternalandexterna
DisplayMessageLevelExternalQ4Sswitchopen(MBCCB3)InternalandexternalswitchesExternalQ5Nswitchopen(MBCorSBCCB2)InternalandexternalswitchesFanfaultMajorF
DisplayMessageLevelNotenoughbypassstaticswitchesFaultorstateofinstallationNotenoughinvertersforloadconnectionFaultorstateofinstallationPersonalization
WorldwideCustomerSupportCustomersupportforthisoranyotherproductisavailableatnocharge:•ContacttheCustomerSupportCenterbytelephoneore-mail.Forlocal,coun
iiMGEGalaxy500040-130kVA480V990-5219-001
AboutThisManualThismanualdescribesthestartup,shutdown,andnormaloperationoftheMGEGalaxy5000withinformationontheuserinterfacedisplayanddisplaymenustruct
OverviewUserInterfaceTheUPSisoperatedusingthecontrolanddisplayinterface.A.GraphicalDisplayB.LoadprotectedLEDC.MinorfaultLEDD.MajorfaultLEDE.HelpkeyF.F
APresstheMenukeytoaccesstheMainMenu.BPresstheHelpkeyforinformationonthepictogramfunctions.Thekeymustbehelddown.MeasurementsTheMeasurementsdisplayscree
StatusTheStatusdisplayscreensconsistofthefollowingStatusscreens:1.PresstheMenukeytoreturntotheMainMenu.2.Usethefunctionkeys↑or↓tohighlightStatusonthed
•TestsLEDs•BuzzerOFF•EnableLCMindications•DisableLCMindications5.Pressthefunctionkey←toselecttherequiredControlsscreen.990-5219-001MGEGalaxy500040-130
Comments to this Manuals