Installation
Symmetra PX 10-40 kW 208 V
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
Warning: ALL safety instructions in the Safety Sheet
990-2984 must be read, understood, and followed when
installing the UPS system. Failure to do so could result in
equipment damage, serious injury, or death.
Warning: The UPS system has no built-in disconnection
devices for AC output and DC input. An AC output over-
current protection and AC output disconnect must be
provided by the customer.
Warning: After the UPS has been electrically wired, do not
start it up. Start-up is commissioned to APC-authorized
personnel only.
Caution: For customer-supplied external batteries, over-
current protection and a disconnection device for the battery
circuits must be provided.
Note: Ensure that the unit is in its final location
prior to the installation.
Cable Entry
Rear Cable Entry
Loosen the screws to remove the plate.
Punch holes as required and reinstall the panel before mounting the
wiring hardware.
Bottom Cable Entry
Loosen the screws to remove the plate.
Punch holes as required and reinstall the panel before mounting the
wiring hardware.
AC Input, AC Output, and Ground
Cable Landings
Caution: Ensure clockwise phase rotation and neutral
location.
Caution: Power terminal lug diameter is 8 mm. Torque value
is 6 Nm..
Connect power input and output wiring to terminate as shown. Route
the input and output cables in separate conduits.
Make ground connections as shown.
Emergency
Power OFF
Switch
Keep EPO
wire routing
isolated and
use separate
EPO conduit
AC
Output
AC
Input
DC Input
(Optional XR)
2
3
4
E
mergency
P
ower OFF
S
witch
K
eep EPO
w
ire routing
i
solated and
u
se separate
E
PO conduit
AC
Output
AC
Input
DC Input
(Optional XR)
Page view 0
1 2 3 4

Summary of Contents

Page 1 - Installation

990-4063F-00107/2007*990-4063F-InstallationSymmetra PX 10-40 kW 208 VIMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONSWarning: ALL safety instruct

Page 2 - APC Maintenance Bypass Panel

2EPO Switch WiringThe UPS must be connected to either a dry contact or a 24 Vdc Emergency Power Off (EPO) switch.The EPO circuit is considered Class 2

Page 3 - Specifications

3APC Maintenance Bypass Panel installation and wiring procedureMount the APC Maintenance Bypass Panel (MBP) on a wall close to the UPS according to t

Page 4 - Contact Information

4Recommended current protection.Input: 175 Amp. 3-Pole AC circuit breaker with 30 kAIC. Note: If your installation does not include an Isolation Tran