CHAPTER 2: BASIC COMMANDS 6 Command Bypass Command Bypass requires utilization of the commands on the PowerView display. This mode is used to bypa
CHAPTER 2: BASIC COMMANDS 7 Language Setting The factory default language of the user interface is English. You can change the language by download
CHAPTER 2: BASIC COMMANDS 8 Language Setting (continued) 6. Locate the language program file to be downloaded into the UPS. See the APC website at
CHAPTER 3: MENU COMMANDS 9 Menu Commands The following sections describe the details of each command. Commands are organized according to the menu
CHAPTER 3: MENU COMMANDS 10 Display Menu The Display Menu allows the user to customize the PowerView display. Display Function Options Date/Time
CHAPTER 3: MENU COMMANDS 11 Diagnostics Menu The Diagnostics Menu provides useful information for troubleshooting. Menu Item Function Fault and D
CHAPTER 3: MENU COMMANDS 12 Logging Menu (continued) Menu Item Function List Event Groups Lists the specific events in each group. Power Events
CHAPTER 3: MENU COMMANDS 13 Setup Menu The Setup Menu allows the user to customize the UPS functionality. Menu Item Function Options Shutdown Se
CHAPTER 3: MENU COMMANDS 14 Setup Menu (continued) Menu Item Function Options Alarms Sets the alarm thresholds. None Redundancy An audible
CHAPTER 4: TROUBLESHOOTING 15 Troubleshooting The PowerView reports various messages on the display, including alarm status and changes in system c
CHAPTER 4: TROUBLESHOOTING 16 Condition PowerView Message Reason Corrective Action AC adequate for UPS but not for bypass. The UPS will functio
CHAPTER 4: TROUBLESHOOTING 17 Condition PowerView Message Reason Corrective Action Redundancy Restored. Power module redundancy loss occurred
CHAPTER 4: TROUBLESHOOTING 18 Condition PowerView Message Reason Corrective Action Redundancy is below alarm threshold. Actual power module redu
CHAPTER 4: TROUBLESHOOTING 19 Condition PowerView Message Reason Corrective Action On Battery. The UPS is in the on-battery mode. The battery
CHAPTER 4: TROUBLESHOOTING 20 Condition PowerView Message Reason Corrective Action Input circuit breaker tripped open. The input circuit breake
CHAPTER 5: SERVICE 21 Service If the UPS requires service, do not return it to the dealer. Follow these steps: 1. Review the problems discussed in
TABLE OF CONTENTS Chapter 1: Overview ...
CHAPTER 1: OVERVIEW 1 Overview This manual provides an overview of operations for the Symmetra® LX and Extended Run Cabinet, including detailed exp
CHAPTER 1: OVERVIEW 2 Navigation Keys Name Sound Function ? Help Short beep Opens context-sensitive help. Enter Short beep Opens the sel
CHAPTER 2: BASIC COMMANDS 3 Basic Commands Supply Power to the UPS This procedure supplies power to the Symmetra LX and does not supply power to t
CHAPTER 2: BASIC COMMANDS 4 Set the Correct Output Voltage 1. Press the ‘Esc’ button until the Main Menu appears. Use the up and down arrow keys t
CHAPTER 2: BASIC COMMANDS 5 5. In approximately 90 seconds, the green Load On indicator will illuminate and this message will appear. UPS LOAD IS