990-2687C 05/2010 Smart-UPS® RT UXI/UXICH Uninterruptible Power Supply SURT 8000/10000 VA 220/230/240 VAC Tower/Rack-Mount 6U English
9 OPERATION Load SMART-UPS RT FRONT DISPLAY Battery Charge Indicator Description Online The Online LED illuminates when the UPS is drawing
10 Feature Function Normal/Bypass Manual bypass enables the user to manually put connected equipment into bypass mode. While in bypass mode the uti
11 USER CONFIGURABLE ITEMS NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, SMART SLOT ACCESSORY CARDS, OR TERMINA
12 NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, SMART SLOT ACCESSORY CARDS, OR TERMINAL MODE. FUNCTION FACTORY DEF
13 CONNECT THE EPO (EMERGENCY POWER OFF) The output power can be disabled in an emergency by closing a switch connected to the EPO. Adhere to na
14 MAINTENANCE, SERVICE Battery Replacement See your dealer or contact APC at the Web site, www.apc.com for information on replacement battery mod
15 TROUBLESHOOTING Use the table below to solve minor installation and operation problems. Refer to the APC Web site, www.apc.com, for assistanc
16 PROBLEM AND POSSIBLE CAUSE SOLUTION BYPASS LED ILLUMINATES The bypass switch has been turned on manually or through an accessory. If bypass is t
17 RADIO FREQUENCY AND WARRANTY INFORMATION Radio Frequency Warnings This equipment has been tested and found to comply with the limits for a Cl
1 Introduction The APC® by Schneider Electric Smart-UPS® RT is a high-performance, uninterruptible power supply (UPS) that provides protection f
2 ATTACH THE BEZEL TO THE UPS HARDWIRING INSTRUCTIONS • Wiring must be performed by a qualified electrician. • Adhere to all national and local
3 1. Switch the UPS input circuit breaker (see A in diagram) and utility circuit breakers OFF. 2. Remove the input access panel, (see B in dia
4 CIRCUIT BREAKERS 8000/10000 VA Input Circuit Breaker The input circuit breaker must be switched on for the UPS to operate. The input circuit brea
5 CONNECT THE EXTERNAL BATTERIES Battery Safety Read and adhere to the following warnings when installing or servicing the external batteries.
6 THIRD PARTY BATTERY SOLUTION Batteries must be Sealed Lead-Acid type. Use 50 A, 250 VDC fuses with an Interrupt rating of ≥ 20,000 A. Ensure that
7 CONNECT EQUIPMENT AND POWER TO THE UPS 1. Connect equipment to the UPS. 2. Turn on all connected equipment. To use the UPS as a master ON/OF
8 TERMINAL MODE TO CONFIGURE UPS PARAMETERS AND PROGRAM THE NUMBER OF BATTERY PACKS Terminal Mode is a menu driven interface that enables enhanced c