APC MGETM GALAXYTM 6000 User Manual

Browse online or download User Manual for UPS batteries APC MGETM GALAXYTM 6000. APC MGETM GALAXYTM 6000 User's Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 46
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
6739381EN/
Installation manual
Single-unit UPS
Modular UPS
Parallel UPS with SSC
Frequency converters
Static Switch Cubicle
MGE
TM
Galaxy
TM
6000
50, 60 Hz
250 - 600 kVA
Page view 0
1 2 3 4 5 6 ... 45 46

Summary of Contents

Page 1 - 250 - 600 kVA

6739381EN/Installation manualSingle-unit UPSModular UPSParallel UPS with SSCFrequency convertersStatic Switch CubicleMGETM GalaxyTM 600050, 60 Hz250 -

Page 2 - Page 2 - 6739381EN/JD

Page 10 - 6739381EN/JDInstallation(to be carried out by qualified personnel only)HandlingPositioning the cubiclesSide clearances provided by the spaci

Page 3 - Contents

6739381EN/Floor loads (figure 5)Cubicle footpadsFig. 533 3333333333four 60 mm dia.footpads with12 mm averagedepth holes forM16 anchor bolts736cubicle

Page 4 - Characteristics

Page 12 - 6739381EN/JDInstallation (cont.)Layout for an installation with two parallel UPSs and a centralised SSCFig. 8auxiliaries cubicle 2(if applic

Page 5 - Characteristics (cont.)

6739381EN/Diagram for a frequency converter with batteriesFig. 12Diagram for a frequency converter without batteriesFig. 11Note:Both the rectifier-inv

Page 6

Page 14 - 6739381EN/JDInstallation (cont.)Example of 2 multi-bypass modular UPS cubicles for redundancy (from 250 to 500kVA)Fig. 14Q3BPQ4S+-+-QF1Q1 Q

Page 7

6739381EN/Example of an installation comprising three modular UPSs with an external maintenance bypass (from 250 to 500 kVA)Fig. 15mains 1earthstatics

Page 8

Page 16 - 6739381EN/JDInstallation (cont.)Connection of power circuits◗ the power cables for the connectionsbetween cubicles are not supplied;◗ open t

Page 9

6739381EN/160kVA to 400kVA modular UPS rectifier-inverter cubiclecross-section AAfront viewCables connect by lugs:◗ mains 1, mains 2 and load:to 40 X

Page 10 - Installation

Page 18 - 6739381EN/JDInstallation (cont.)250kVA to 450kVA frequency converter or parallel UPS with SSC rectifier-inverter cubiclecross-section AAfron

Page 11 - Installation (cont.)

6739381EN/500kVA single-unit UPS rectifier-inverter cubiclecross-section AAfront viewHeight of connections relative to floor:◗ mains 1: 450 mm ;◗ main

Page 12

Page 2 - 6739381EN/JD

Page 13

Page 20 - 6739381EN/JDInstallation (cont.)500kVA modular UPS rectifier-inverter cubiclecross-section AAfront viewHeight of connections relative to flo

Page 14

6739381EN/Installation (cont.)500kVA frequency converter or parallel UPS with SSC rectifier-inverter cubiclecross-section AAfront view600kVA parallel

Page 15

Page 22 - 6739381EN/JD500/800kVA Static Switch CubicleHeight of connections relative to floor:◗ mains 2: 1050 mm max.;◗ inverter outputs and load: 570

Page 16

6739381EN/1200kVA Static Switch Cubiclecross-section AAfront viewCables connected by lugs to 80 x 8 mmcopper terminals and 14 mm diameterholes.Height

Page 17

Page 24 - 6739381EN/JDBattery cubicle (example of cubicle containing battery circuit breaker QF1)cross-section AAfront viewThis battery cubicle shown

Page 18

6739381EN/1200kVA external maintenance bypass cubicleKey to figure:AA: cross-section AA of cubicle,B: cubicle front view,C: front panel,E: connection

Page 19

Page 26 - 6739381EN/JDConnection of "Media Contacts 9" standard auxiliary circuits (figure 16)The standard auxiliary circuits of therectifie

Page 20

6739381EN/Fig. 17Connections between rectifier-inverter cubiclesConnections between cubiclesEmergency shutdownThe UPS emergency shutdownfunction is ge

Page 21

Page 28 - 6739381EN/JDMISIboardUPS 1MISIboardUPS 2MISIboardUPS 3AXM5XM6XM7XM10XM11XM12XM5XM6XM7XM10XM11XM12XM5XM6XM7XM10XM11XM12ACPZ boardrectifier-in

Page 22

6739381EN/ImportantOutside the cubicles, group the cablesbetween the MISI boards and thosebetween the APOZ boards with theother auxiliary links betwee

Page 23

6739381EN/ContentsCharacteristicsCharacteristics common to all cubicles ... 4Rectifi

Page 24

Page 30 - 6739381EN/JDFig. 22Connection of "Media Contacts 15" additional auxiliary circuits (option) (figure 22)The additional auxiliary ci

Page 25

6739381EN/Connection of the battery "Temperature Monitor" (for a single-unit UPS)Connection of the battery "Temperature Monitor" (

Page 26

Page 32 - 6739381EN/JDQF1self-adhesive"on" lightmountingbracketstie thecableto thecubicleuprighttie the cableto the cubicleuprightto rectifi

Page 27

6739381EN/Installation (cont.)Link to an IBM AS/400® computerConnections:◗ connections are made to the femaleclient connectors XR1 and XR2 on the"

Page 28

Page 34 - 6739381EN/JD112112112112XR1 XR2XR3XR4remoterelay board123456789101112connector XR1output signals:connector XR2123456789101112low battery shu

Page 29

6739381EN/Appendix (to be carried out by qualified personnel only)Mains 2 line protectionUPS 250 to 450kVArated inverter output maximum permissible cu

Page 30

Page 36 - 6739381EN/JDCubicle mounting and connection for 600kVA UPSsCubicle mountingGusset plates have been fitted to thetop corners on all four side

Page 31

6739381EN/AAL1L2transformercable tie barmains 1L3batteryL+Lrectifierchargerinverterstackinverterstackinverterstackspacinguprightscabletie barair extra

Page 32

Page 38 - 6739381EN/JDAAXR7XR6XR5XR9XR8XR4XR2XR1Q4SXR3L1 L2 L3NL1 L2 L3NonoffQ3BPonoffQ5Nonoffinverterstackinverterstackinverterstackspacinguprightsca

Page 33

6739381EN/inverterstackinverterstackinverterstackspacinguprightscabletie barair extractionairadmissionairadmissionconnectionfrom belowtrough (if appli

Page 34

Page 4 - 6739381EN/JDCharacteristicsCharacteristics common to all cubiclesMGETM GalaxyTM 6000 UPS: example of a rectifier-inverter cubicle◗ After movi

Page 35 - Mains 2 line protection

Page 40 - 6739381EN/JDNL1L3L2NL1L3L2Q5NQ3BPQ4SonoffonoffonoffL1 L2 L3NXF1-XF2XM1-XM2 K2Sspacinguprightscard cageearth strap to be connectedto the fron

Page 36 - Appendix (cont.)

6739381EN/Right cubicle of a 2000kVA Static SwitchCables connected by lugs to5 x (5 x 100) mm copper terminals and16 mm diameter holes.Height of conne

Page 37

Page 42 - 6739381EN/JDCables connected by lugs to5 x (5 x 100) mm copper terminals and16 mm diameter holes.Height of connections relative to floor:◗ i

Page 38

6739381EN/Appendix (cont.)Details of earthing connections in the various cubicles250 to 400kVA rectifier-inverter cubicle450 - 500kVA rectifier-invert

Page 39 - (cont.)

Page 44 - 6739381EN/JD120 to 1200kVA Static Switch Cubiclesconnection with a bolt,nut and contact washermains 2AIRZtransformerearth barinputdoorframei

Page 40 - Internal connections between

6739381EN/Appendix (cont.)2000kVA Static Switch CubiclesSYNIconnection witha bolt, nut andcontact washerdoordoordoorframedoorframeearth bar earth barm

Page 41

Page 46 - 6739381EN/JD6739381EN-JD

Page 42

6739381EN/Rectifier-inverter cubiclesCharacteristics of rectifier-inverter cubiclesrated cubicle cubicle cubicle maximuminverter width W height H dept

Page 43

Page 6 - 6739381EN/JDCharacteristics (cont.)Electrical parameters for selecting protective devicesratedinverteroutputin kVAfor 25% for 50%overload (3)

Page 44

6739381EN/Electrical parameters for determining cable cross-sections◗ the battery current values and cablecross-sections have been determinedfor a bat

Page 45 - "Tele-Monitor" unit

Page 8 - 6739381EN/JDCharacteristics (cont.)The table opposite serves as anexample for an installation comprisingup to four frequency converters or fo

Page 46 - 6739381EN-JD

6739381EN/Installation comprising modular UPSs with an external maintenance bypassFig. 3The table opposite serves as anexample for an installation wit

Comments to this Manuals

No comments