InRow RD Fluid Cooled Operation and Maintenance20
Beeper Volume. Set the volume (Low, Medium, High or OFF) of the audible tone that sounds every
time a key is pressed on the display interface.
Beep on Alarm. Set to ON or OFF. When set to ON, the cooling unit will sound an audible tone every
30 seconds when a new alarm occurs. Silence the audible tone by pressing any key on the display
interface. When the alarm clears itself, the tone will stop on its own.
Display units
Path: Main > Set Display Units
Set the units of measure for the cooling unit to either US or Metric.
Network Configuration
The cooling unit is shipped with a Network Management Card that enables the cooling unit to be
managed over a network. Configure the network settings for the Network Management Card for this
cooling unit from the display interface. The management card allows remote control and configuration
of the equipment.
Configure network
Path: Main > Configure Network
MAC Address.
Displays the unique network identifier which was assigned to the Network
Management Card of this cooling unit at the factory.
IP Address. You will be prompted to enter an Admin password. Enter the password and press ENTER to
return to the IP screen. Press
ENTER again to change the network settings for Manual boot mode only.
IP: Enter the IP address assigned to the Network Management Card of this cooling unit.
SM: Enter the subnet mask for the Network Management Card of this cooling unit.
GW: Enter the default gateway for the Network Management Card of this cooling unit.
Boot Mode. Set the method by which the Network Management Card of the cooling unit acquires
network settings.
Manual: Enter the IP address, subnet mask, and default gateway using the IP Address menu.
BootP: Set the Network Management Card of the cooling unit to obtain its network settings from
a BOOTP server.
DHCP: Set the Network Management Card of the cooling unit to obtain its network settings from
a DHCP server.
By default, DHCP requires an APC cookie before it will accept an IP address. See
“BOOTP & DHCP configuration” on page 28 for more information.
BootPDHCP: Set the Network Management Card of the cooling unit to search for its network
settings from either a BOOTP or a DHCP server.