39InRow RD Fluid Cooled Operation and Maintenance
Quarterly Preventive Maintenance
Perform all the Monthly Preventive Maintenance items and the items below.
Prepared By: _________________________________
Model Number: _______________________________
Serial Number: _______________________________
Date: ______________________________________
Mechanical
Electrical Hazard: Turn off the cooling unit, disconnect all power sources and perform
lockout/tagout procedures before performing any electrical or mechanical service. Wear
appropriate personal protective equipment when checking hazardous voltages.
Verify that the fan hardware is tight.
Clean or replace the air filters.
Clean the condensate drain line.
Clean the dust from door perforations.
Clean the dust from fan bezels.
Clean and inspect the inline chilled water strainer.
Functional tests
Verify the cooling operation mode is functioning properly.
Verify the operation of the chilled water actuator.
Semi-Annual Preventive Maintenance
Perform all the Monthly/Quarterly Preventive Maintenance items and the items below.
Prepared By: _________________________________
Model Number: _______________________________
Serial Number: _______________________________
Date: ______________________________________
Cleanliness
Check the cleanliness of the evaporator coil. Clean if required.