17InRow Fluid Cooled RD Installation
Service access
A minimum of 900 mm (36 in) of clear floor space in front of and behind the equipment is
recommended for service. All required periodic maintenance can be performed from the front or rear of
the equipment.
Most of the cooling components in the equipment (e.g. dry filter, sight glass, solenoid, and expansion
valves) must be brazed for repair or replacement. Do not service these components while the equipment
is located inside the data center. Use the casters on the equipment to move it outside the data center for
service. A minimum of 914 mm (36 in) of clear floor space in front of or behind the equipment is
recommended to roll out the equipment.
Note: Check local and national codes and regulations for additional service access
requirements.
Dimensions are shown in mm (in).
na2230a
Service access
when equipment is
inside the row
Free space needed
to move equipment
outside the row