23InRow Fluid Cooled RD Installation
Electrical Connections
The electrical connections required in the field are:
Controls (display interface, Network Management Card)
Communication (A-Link, Building Management System)
Power to InRow RD (single phase plus ground)
All electrical connections must be in accordance with applicable industry guidelines as well as national
and local codes and regulations.
See the equipment nameplate for voltage and current requirements.
Make all low-voltage connections, including data and control connections, with properly insulated wires.
Insulation of low-voltage wiring must be rated for at least the voltage of any adjacent wiring.
Electrical Hazard:
Potentially dangerous and lethal voltages exist within this equipment.
More than one disconnect switch may be required to energize or de-energize this equipment.
Observe all cautions and warnings. Failure to do so could result in serious injury or death.
Only qualified service and maintenance personnel may work on this equipment.
Electrical Hazard: The equipment must be grounded. Check the equipment nameplate for
correct ratings.
Warning: Use a voltmeter to ensure that power is turned off before making any
electrical connections.
Control connections
Note: Wire all low voltage input and output connections as Class 2 circuits.
Depending on the configuration, additional control connections may be required for the A-Link remote
communications through APC Network Management Card support or traditional equipment-monitoring
software.