InRow Fluid Cooled RD Installation26
Rack temperature sensor
The rack temperature sensor monitors and controls the equipment
airflow and ensures an adequate supply of cooling air to the server
racks in the data center.
The equipment is supplied with an external rack temperature
sensor. See “Installation kit inventory” on page 5. This sensor,
along with wire clamps and wire clips, are included in the
installation kit shipped with the equipment.
Installing the rack temperature sensor
Note: Rack temperature sensor installation is not required if the equipment operates in Rack
Air Containment System (RACS) or Hot Aisle Containment System (HACS) mode. For more
information about those systems, see www.apc.com. The InRow configuration requires
temperature sensor installation.
1. Insert the rack temperature sensor connector in the temperature sensor port at the user interface.
See “User interface connections” on page 24.
a. For a top installation, push the rack temperature
sensor through the access hole located at the top
of the equipment.
b. For a bottom installation, route the sensor
through the access hole in the bottom of the
equipment.
2. Route the sensor through either the top or the bottom
of the adjacent server rack.
3. Secure the temperature sensor cable to the front door
of the adjacent server rack at multiple locations using
the provided wire clips as shown. See “Installation kit
inventory” on page 5.
Install the sensor where lack of sufficient cooling air
is most likely. The optimum position of the rack temperature sensor will vary from installation to
installation, but must be located in the airflow to allow proper readings.
Servers most likely to have insufficient or inadequately cooled air due to the recirculation of hot
air from the hot aisle include:
a. Servers positioned at the top of a rack.
b. Servers positioned at any height in the last rack at an open end of a row.
c. Servers positioned behind flow-impairing obstacles such as building elements.
d. Servers positioned in a bank of high-density racks.
e. Servers positioned next to racks with Air Removal Units (ARU).
f. Servers positioned very far from the equipment.
g. Servers positioned very close to the equipment.
gen0744a
gen0767a
Wire clip
Temperature
sensor