InstallationInRow® RDFluid CooledACRD200ACRD201DATA CENTER SOLUTIONSFor More Information:(866) [email protected]
InRow RD Fluid Cooled Installation4Model IdentificationThe model number can be found on the outside of the shipping crate and on the nameplate located
5InRow RD Fluid Cooled InstallationComponent IdentificationInstall kitNote: Do not discard the install kit.The install kit contains items which may be
InRow RD Fluid Cooled Installation6Exterior components (front)Item Description Item Description1Removable rear door6Adjustable leveling foot2Side pane
7InRow RD Fluid Cooled InstallationInterior components (front)Item Description Quantity Item Description Quantity1Electrical control box (retractable)
InRow RD Fluid Cooled Installation8Interior components (rear)Item Description Quantity Item Description Quantity1Filter/dryer 17Electrical control box
9InRow RD Fluid Cooled InstallationElectrical panelItem Description Item Description1Leak detector port6Building management system (BMS) RS-485 port2R
InRow RD Fluid Cooled Installation10Top piping and power access locationsBottom piping and power access locationsItem Description Item Description1Ele
11InRow RD Fluid Cooled InstallationPiping DiagramsNote: Top or bottom entry can be chosen individually for each type of connection, i.e. power, conde
InRow RD Fluid Cooled Installation12Glycol cooled pipingNote: Bottom piping shown.Item Description Item Description1Expansion tank*8Gate valves*2Tank
13InRow RD Fluid Cooled InstallationConnections OverviewAll connections to and from the equipment can be made through either the top or the bottom of
This manual is available in English on the enclosed CD.Dieses Handbuch ist in Deutsch auf der beiliegenden CD-ROM verfügbar.Deze handleiding staat in
InRow RD Fluid Cooled Installation14Room PreparationAir distributionThe equipment distributes air in a back-to-front discharge pattern, removing hot a
15InRow RD Fluid Cooled InstallationInstallationRemoving Doors and PanelsDoor removalSide panel removalna2631aWarning: All doors and side panels must
InRow RD Fluid Cooled Installation16Positioning the EquipmentRemove the compressor shipping bracketCaution: Failure to complete the following steps ma
17InRow RD Fluid Cooled InstallationService accessA minimum of 900 mm (36 in) of clear floor space in front of and behind the equipment is recommended
InRow RD Fluid Cooled Installation18Leveling the EquipmentNote: The leveling feet at the corners of the equipment provide a stable base if the floor i
19InRow RD Fluid Cooled InstallationJoining the Equipment to EnclosuresJoining to NetShelter® SX enclosuresThe equipment comes with four joining brack
InRow RD Fluid Cooled Installation20Mechanical ConnectionsLiquid pipingNote: Install all piping in accordance with applicable industry guidelines as w
21InRow RD Fluid Cooled InstallationRouting the condensate pump drain line. Route the condensate drain line through the top or the bottom of the equip
InRow RD Fluid Cooled Installation22Leak sensor (optional)Install one leak sensor (AP9325). To extend the leak sensor length, add up to three addition
23InRow RD Fluid Cooled InstallationElectrical ConnectionsThe electrical connections required in the field are:• Controls (display interface, Network
American Power Conversion Legal DisclaimerThe information presented in this manual is not warranted by the American Power Conversion Corpora-tion to b
InRow RD Fluid Cooled Installation24User interface connections1A-Link ports: Pin 1-High; Pin 2-Low; Pins 3, 6-Perf Power; Pins 4, 5-Ground<Alarm NO
25InRow RD Fluid Cooled InstallationForm C alarm contacts and shutdown inputSee items 6 through 13 in “User interface connections” on page 24. A relay
InRow RD Fluid Cooled Installation26Rack temperature sensorThe rack temperature sensor monitors and controls the equipment airflow and ensures an adeq
27InRow RD Fluid Cooled InstallationA-Link connectionsThe A-Link bus connection allows multiple InRow RDs (up to twelve) to communicate with one anoth
InRow RD Fluid Cooled Installation28Building Management System (BMS)The Modbus interface allows each InRow RD to communicate with the BMS. Use a three
29InRow RD Fluid Cooled InstallationNetwork port1Network port2LAN cable (10/100 Base-T)na2679aSwitch/HubInRow RD #1 InRow RD #2 Final InRow RD
InRow RD Fluid Cooled Installation30OHE connectionsWiring configurationsRoute incoming power to the electrical junction box located at the top or bott
31InRow RD Fluid Cooled InstallationTop routing1. Remove the electrical junction box cover. 2. Route electrical cabling into the electrical junction b
InRow RD Fluid Cooled Installation32SpecificationsNote: For additional capacity and performance data, consult the InRow RD Tec hnical Data Manual avai
Radio Frequency InterferenceChanges or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s
9/2010990-3213B-001APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following
ContentsInRow RD Fluid Cooled InstallationiGeneral Information... 1Overview . . . . . . . . . .
InRow RD Fluid Cooled InstallationiiInstallation... 15Removing Doors and Panels . .
1InRow RD Fluid Cooled InstallationGeneral InformationOverviewSave these instructionsThis manual contains important instructions that must be followed
InRow RD Fluid Cooled Installation2Safety Note: All work should be performed by American Power Conversion (APC®) authorized personnel only. Follow all
3InRow RD Fluid Cooled InstallationInspecting the EquipmentYour American Power Conversion (APC) InRow® RD air conditioner has been tested and inspecte