Output
Output Power Capacity 280 Watts / 450 VA
Max Configurable Power 280 Watts / 450 VA
Nominal Output Voltage 120V
Output Voltage Distortion Less than 5% at full load
Output Frequency (sync to mains) 47 - 53 Hz for 50 Hz nominal,57 - 63 Hz for 60 Hz nominal
Crest Factor up to 5 : 1
Waveform Type Stepped approximation to a sinewave
Output Connections
(4) NEMA 5-15R
Input
Nominal Input Voltage 120V
Input Frequency 50/60 Hz +/- 3 Hz (auto sensing)
Input Connections
NEMA 5-15P
Cord Length 1.83 meters
Input voltage range for main
operations
82 - 144V
Input voltage adjustable range for
mains operation
75 - 154V
Batteries & Runtime
Battery Type Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Typical recharge time 5 hour(s)
Replacement Battery RBC18
RBC™ Quantity 1
Typical Backup Time
at Half Load
19.4 minutes (140 Watts)
Typical Backup Time
at Full Load
5.9 minutes (280 Watts)
Runtime Chart Smart-UPS SC
Communications & Management
Interface Port(s) DB-9 RS-232