APC AIS 3000 User Manual Page 3

  • Download
  • Add to my manuals
  • Print
  • Page
    / 5
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 2
Output
Output Power Capacity 12 kW / 15 kVA
Max Configurable Power 12 kW / 15 kVA
Nominal Output Voltage 120V,208V,208V 3PH
Output Voltage Note Configurable for 208 and 220V - 3 Phase
Efficiency at Full Load 93%
Output Voltage Distortion Less than 5% at full load
Output Frequency (sync to mains) 57 - 63 Hz for 60 Hz nominal
Crest Factor Unlimited
Waveform Type Sine wave
Output Connections
(1) Hard Wire 5-wire (3PH + N + G)
(1) Screw Terminals
Bypass Built-in Maintenance Bypass,Built-in Static Bypass
Input
Nominal Input Voltage 208V 3PH
Input Frequency 40 - 70 Hz
Input Connections
Hard Wire 5-wire (3PH + N + G)
Input voltage range for main
operations
160 - 240V
Other Input Voltages 220
Batteries & Runtime
Battery Type VRLA
Included Battery Modules 2
Available Battery Slots 2
Typical recharge time 5 hour(s)
RBC™ Quantity 2
Typical Backup Time
at Half Load
28.1 minutes (6000 Watts)
Typical Backup Time
at Full Load
10.0 minutes (12000 Watts)
Runtime Chart AIS 3000
Page view 2
1 2 3 4 5

Comments to this Manuals

No comments