APC SUDP6000I Service Manual Page 21

  • Download
  • Add to my manuals
  • Print
  • Page
    / 54
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 20
990-1008, Revision 1, 4/9917
6.4 Smart-UPS DP not able to switch to normal operation.
MAINS
OUTSIDE
TOLERENCE
CHECK SIGNAL
FROM MEAS. &
SUPPLY TO
CONTROLLER iN
64-POLE PLUG
FAULT IN 64-POLE
PLUG BETWEEN
CONTROLLER
AND MEAS. &
SUPPLY. CHANGE
MEAS. & SUPPLY.
FAULT IN
CONTROLLER
FUSES IN MEAS. &
SUPPLY OR
MEAS. & SUPPLY
DEFECT
START
CORRECT
SIGNAL?
END
NO
YES
IS MAINS
OKAY? VOLTAGE
FREQ...
WAVEFORM?
POSSIBILITY
OF CONNECTING
E.G. DPM OR
CALIBRATION SW
TO UPS?
IS MAINS OKAY?
STEP 86 IN
CALIBRATION SW.
YES
YES YES
NO
NO
Page view 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 53 54

Comments to this Manuals

No comments