8.0 Storing the UPS
8.1 Storage conditions
The UPS should be covered and stored upright in a cool dry location. The UPS should
be stored with its battery in a fully charged state. That is, the indicated battery capacity
should be 100% before the UPS is switched off for storage. Disconnect accessories or
cables connected at the computer interface port as such devices may unnecessarily
drain battery charge.
8.2 Extended storage
To achieve expected run time following extended storage, the UPS should be allowed
to refresh its batteries every 6 months in environments where the ambient temperature
is -15°C to +30°C (5°F to 86°F). For extended storage in environments where the ambient
temperature is +30°C to +45°C (86°F to 113°F), the UPS should be allowed to refresh its
batteries every 3 months.