1User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Copyright © 1999 APC Denmark A/SDue to continuous product development informationgiv
10 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03WARNING!If the UPS is out of service formore than 48 hours theconnected batteries
11User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 0310. Turn all input switches (Q001) to position “0“.On systems with dual utility, tu
12 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03DP300EDP300EQ010aQ001aQ002aQ004Q010bQ001b Q002bUtility 1Q003Service bypass switchH
13User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03The following can be carried out on any UPS14. Press on the keyboard15. Press or
14 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03DP300EDP300EQ010aQ001aQ002aQ004Q010bQ001b Q002bUtility 1Q003Service bypass switchH
15User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Operation3.0 OperationThe display is used to show parameters, alarms/messages, and
16 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 034.0 Programming Parameters4.1 GeneralSome operating parameters can be programmed d
17User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Programming Parameters4.2.2 Keys used for programming4.2.3 Programming example - sw
18 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 034.3 Programming of system configuration parametersThe system configuration paramet
19User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Programming Parameters4.3.2 Programming example – change charge voltage to 446V*Act
2 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONSThis manual contains important
20 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 034.4 Programming of battery monitorAction Display shows1. Press and simultaneous
21User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Programming Parameters4.5 Parallel programming/operationProgramming parameters for
22 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Programming ParametersAction Display shows1. Press and simultaneously to openfor
23User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Parallel operation alarms.General.If alarms concerning the parallel operation commu
24 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Measurements98.01.1610.22,13Mains 1 voltage480 480 480 VacBattery current+ 20 AdcM
25User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Alarms6.0 Alarms - What To Do6.1 GeneralAlarms are indicated by the red LED (above
26 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Alarms6.4 The events loggerThe events logger is a memory stack, in which the last
27User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Alarms6.6 Possible alarmsPossible alarm1. Peak current limiter active2. Bypass powe
28 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03AlarmsPossible alarmDescription Action20. High temp. isolationtransformer21. High
29User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03AlarmsPossible alarm Description Action39. System is locked in oper.mode40 RAM1 mem
3User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Table of Contents:1.0 Introduction1.1 General1.2 The display unit2.0 Stop, Start &am
30 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 037.0 Remote Display7.1 Remote Display OperationThe remote display is an inactive un
31User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Remote DisplayPossible alarm DescriptionBattery MCB is off Battery MCCB switch not
32 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 038.0 Preventive Maintenance8.1 GeneralThe maintenance of the Silcon DP300E UPS syst
33User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03WARNING!The UPS must at least be inoperation for min. 16 hours in a3 month period t
34 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Preventive Maintenance8.5 Battery monitor testThe battery monitor has two main pu
35User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Preventive Maintenance8.5.4 Operation of the battery monitorThe operation of the ba
36 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03NOTE:When using economy modethere is NO power factorcorrection on the input orregu
37User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 0310.0 System Specifications10.1 Technical dataInput Voltage 3 x 480VVoltage toleranc
38 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 0311.0 How to Contact APCHow to Contact APCFor more information call:Tel: (800) 800-
4 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Introduction1.0 Introduction1.1 GeneralCongratulations on your choice of Silcon DP3
5User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Stop, Start & Operating the External Service Bypass Panel2.0 Stop – Start and Op
6 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 031. Prepare the system by opening the front door(s).2. Continue with the next point
7User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Start up of system now completed.2.5 Start (from complete power down)2.5.1 Starting
8 User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Single UtilityDual Utility2.6 Operating the external service bypass switch, single
9User Guide Silcon DP300E Series 480V 120-160kVA7OA0003 US rev. 03Action1. Turn the input switch (Q001) to position “1”.If dual utility is present, tu
Comments to this Manuals