22 Smart-UPS RT 15000/20000 VA 230 Vac UXI/UXICH Tower User Manual
Troubleshooting Display Messages
Use the table below to solve minor installation and operation problems. Refer to the APC Web site,
www.apc.com for assistance with complex UPS problems.
The PowerView reports various messages on the display, including alarm status and changes in system
configuration. This section lists all the PowerView display messages, the reason for the message, and the
appropriate corrective action.
Messages may occur simultaneously. If this happens, be sure to review all of the messages for a better
understanding of the system condition.
Condition
PowerView Display
Message
Reason for Message Corrective Action
Start-Up #Batteries changed since
last ON.
At least one battery module has been
added or removed from the UPS since
the last time the Pwr ON command
was issued.
No corrective action necessary.
Proceed with the start-up.
Automatic Self Test
Started.
The UPS has started pre-programmed
battery test.
Batt capacity less than
Return Batt Cap.
The battery capacity of the UPS is less
than the user-specified minimum
battery capacity required to turn on
the load.
Option 1) Abort the start-up and
allow batteries to recharge.
Option 2) Continue start-up, with less
than minimum battery capacity.
System Start-Up
Configuration Failed.
System configuration error: Start-up
diagnostic fault.
Check for other alarms.
If the problem persists contact APC
Customer Support. Refer to Contact
Information in this manual.
Mains: Site Wiring Fault Input and Output Jumpers are not
configured correctly
Check input wiring tray jumpers and
output shorting jumper for
compatibility. Refer to the Input/
Output Jumper Configurations table
in this manual.
Bypass Not Available -
Wrong Ph Seq
Check bypass jumpers in input
wiring tray and output shorting
jumper for compatibility. Check
bypass phases for positive sequence.
Refer to the Input/Output Jumper
Configurations table in this manual.
Bypass: Site Wiring Fault Check bypass jumpers in input
wiring tray and output shorting
jumper for compatibility. Refer to the
Input/Output Jumper Configurations
table in this manual.